2009-03-06 09:50:18 | |
| |
| |
| APPLICATION #09020560 ELECTRICAL PLAN REVIEW |
| 836 ALMERIA ROAD #836-840 3/5/09 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE RISER DIAGRAM INDICATES ONE METER AND TWO |
| PANELS, THE PLAN LOCATES TWO METERS AND TWO MAIN |
| DISCONNECTS. CORRELATE THE PLAN AND THE RISER AS TO THE |
| INTENT OF THE DESIGNER. ALSO SEE 230.2 NUMBER OF |
| SERVICES |
| A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| ONE SERVICE. |
| |
| 2} THERE ARE NO MAIN DISCONNECTS ON THE RISER, BUT |
| INDICATED AT THE BUILDING. 215.5 |
| |
| 3} SEE 250.66 REGARDING GEC SIZE AND LOCATION. LOCATION |
| WILL BE DETERMINED BY COMMENT #2 RESPONSE |
| |
| 4} THE PANEL LOCATION IN THE UNITS ARE IN VIOLATION OF |
| 110.26 SPACING REQUIREMENTS. |
| |
| 5} 210.11(C) (1) SMALL-APPLIANCE BRANCH CIRCUITS IN |
| ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE |
| SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR |
| ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B).***ONLY |
| ONE ON THE SCHEDULE. |
| |
| 6} CIRCUIT #11 IS LABELED "LAUNDRY ROOM" BUT APPEARS TO |
| BE LIVING ROOM. ALSO IT DOES NOT MEET THE REQUIREMENTS |
| OF A LAUNDRY ROOM CIRCUIT PER 210.11(C)(2). |
| |
| 7} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED |
| UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY |
| IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS AMENDED |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |