2009-03-31 11:59:15 | RESIDENTIAL (R3) REPAIR/RENOVATION BUILDING REVIEW |
| CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| REVISIONS. |
| |
| 1- CLARIFY WHICH UNIT IS GOING TO BE REPAIRED. ADDRESS |
| ON PERMIT APPLICATION IS FOR 836 ALMERIA RD. FLOOR |
| PLANS STATE THAT UNIT 836 TO REMAIN AS IS. COORDINATE |
| INFORMATION AS REQUIRED TO MATCH. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| |
| 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ENTRY AND REAR SWING DOORS. NOA 02-1211.12 SUBMITTED |
| EXPIRED ON APRIL 14, 2008. NEED TO PROVIDE CURRENT ONE. |
| |
| B) EXTERIOR LOUVER SHOWN GABLE WALL ON NORTH ELEVATION. |
| |
| C) ALL SIMPSON STRUCTURAL CONNECTORS SHOWN ON PLANS AND |
| DETAILS. GO TO WWW.FLORIDA BUILDING.ORG. PROVIDE ONLY |
| COPY OF THE FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| PAGE SHOWING CONNECTOR. NO NEED TO DOWNLOAD COMPLETE |
| REPORT. NOTE: THIS APPLIES TO STRUCTURAL CONNECTORS |
| ONLY. OTHER PRODUCT APPROVALS NEED TO PROVIDE COMPLETE |
| REPORT. |
| |
| 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING ALL |
| PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC 2004. |
| ALSO, MISSING APPROVAL ON SHINGLES PRODUCT APPROVAL. |
| |
| 5- ENERGY CALCULATIONS SUBMITTED: |
| A) PROVIDE REVISED FORM 600C-04R. |
| |
| B) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| |
| C) CLARIFY ITEM #8A. ACCORDING TO WALL SECTIONS SHOWN |
| ON DRAWINGS THERE IS NOT SLAB ON GRADE. SEE PLANS AND |
| REVISE AS REQUIRED. |
| |
| 6- ARCHITECT TO PROVIDE THE ARCHITECTURAL FIRM LICENSE |
| NUMBER ON TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 |
| OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA |
| STATUTE. UNABLE TO FIND AA-C002146 ON STATE WEBSITE. |
| |
| 7- PLANS TO SPECIFY SIZE AND LOCATION OF ATTIC ACCESS. |
| SEE SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN. |
| SIZE, LOCATION AND CLEARANCE REQUIREMENTS. |
| |
| 8- SHEET A-4: |
| A) REVISE NOTES BELOW STRUCTURAL WOOD NOTE #6. THIS |
| BUILDING HAS NO HIP ROOF, BUT GABLE ROOF. REFERENCE |
| CODE SECTIONS FOR DRAFSTOPPING FROM THE 2004 FLORIDA |
| RESIDENTIAL CODE WHICH IS THE CODE THAT GOVERNS ONE AND |
| TWO FAMILY BUILDINGS. |
| REVISE DIMENSIONS FOR ATTIC ACCESS. SEE SEC. R807 OF |
| 2004 FLORIDA RESIDENTIAL CODE. ALSO, REFERENCE PROPER |
| SECTION FROM THE RESIDENTIAL CODE. SEE COMMENTS ON |
| PLANS. |
| |
| B) REVISE DESIGN WIND LOADS SPECIFICATIONS. ASCE YEAR |
| REFERENCE TO BE USED IS ASCE 7-02, NOT 98. CLARIFY IF |
| STRUCTURE IS DESIGNED USING ASCE 7-02 OR FBC 2004 SEC. |
| 1609. REVISE NOTE STATING THAT THIS IS A BUILDING WITH |
| A HIP ROOF. THIS IS A BUILDING WITH GABLE ENDS. REVISE |
| ROOF SHEATHING SPECIFICATIONS TO COMPLY WITH SEC. |
| R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. NEED TO |
| IDENTIFY ROOF ZONE #3 AND MINIMUM NAIL TYPE AND SPACING |
| TO BE USED. NEED 8D RING SHANK NAILS AT 4"O.C. AT EDGES |
| AND INTERMEDIATE SUPPORTS. REVISE AS REQUIRED. SEE |
| FIGURE 803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR |
| ROOF SHEATHING NAILING ZONES. |
| |
| C) SPECIFY ALL LIVE LOADS, INCLUDING THE ATTIC LIVE |
| LOADS AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| TENANT SEPARATION WALL TO VERIFY COMPLIANCE WITH SEC. |
| R317 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| E) REVISE SPECIFICATIONS FOR TRUSS CONNECTOR H10A. SEE |
| PRODUCT APPROVAL FOR CORRECT UPLIFT CAPACITY AND |
| SPECIFIED NUMBER OF NAILS. OTHERWISE PROVIDE COMPLETE |
| ENGINEERING ANALYSIS FOR NUMBERS THAT DIFFER FROM THOSE |
| TESTED AND PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH |
| DESIGN PRESSURES OF SEC. R301. |
| |
| F) COORDINATE LOCATION OF ATTIC ACCESS WITH ITEM #7 |
| ABOVE. |
| |
| 9- SHEET A-5: |
| A) REVISE PRE-ENGINEERED WOOD TRUSSES NOTES: COORDINATE |
| THE DESIGN LOADS WITH THOSE SHOWN ON SHEET A-4 AND |
| INCLUDE THE ATTIC LIVE LOADS. REFERENCE CORRECT CODE |
| SECTION AND CODE YEAR. ALSO, UPDATE YEAR EDITION OF |
| ASCE 7. REFER TO ASCE 7-02 NOT 98. SEE COMMENTS ON |
| PLANS. |
| |
| B) TYPICAL NEW WALL SECTION: REVISE ROOF SHEATHING |
| NOTE. COORDINATE WITH ITEM #8B ABOVE. COORDINATE WITH |
| ROOF SHINGLES NOTE ON SAME DRAWING. COORDINATE TRUSS |
| AND WALL CONNECTORS WITH THOSE SHOWN ON SHEET A-4. |
| REVISE NOTE REGARDING THE HIP ROOF. SPECIFY SIZE OF |
| CONTINUOUS VENT TO VERIFY COMPLIANCE WITH SEC. R806 OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 10- PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE |
| DONE TO ORIGINAL DRAWINGS TO EXPEDITE THE REVIEW |
| PROCESS. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |