Plan Review Notes For Permit 09020551 |
Permit Number |
09020551 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-03-05 09:43:34 | | | | | PROVISO | | | | THIS REVIEW IS BEING PASSED TO FACILITATE THE STARTING | | OF THIS PROJECT, THE ELECTRICAL SUBMITTALS HOWEVER ARE | | INCOMPLETE. PLEASE RESUBMIT A LOAD CALCULATION PRIOR TO | | CALLING ROUGH ELECTRICAL INSPECTION. THE REVIEWED | | CALCULATION MUST BE ON THE JOB SITE AT TIME OF | | INSPECTION. ALLOW AT LEAST ONE WEEK (PER TRADE) FOR | | PLAN REVIEW. THE CONTRACTOR MAY PROCEED AT HIS OWN | | RISK. THE ELECTRICAL SERVICE MAY HAVE TO BE UPGRADED. | | | | PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL SERVICE, | | INDICATING ALL EXISTING LOADS AND ALL LOADS TO BE | | IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 NEC | | 2005. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|