2009-10-05 08:14:49 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED (SAME |
| PLANS SUBMITTED, NOT SIGNED & SEALED, ONLY ONE SET): |
| |
| 1. ADDRESSED. |
| |
| 2. PLANS ARE NOTED AS PRELIMINARY. PERMIT DOCUMENTS MAY |
| BE SUBMITTED TO EXPEDITE THE PROCESS (OPTIONAL; NOT |
| REQUIRED). THE PLANS WILL BE REVIEWED AND STAMPED WITH |
| A FAILED REVIEW STATUS. WHEN CONTRACTOR HAS BEEN |
| SELECTED, CONTRACTOR CAN THEN APPLY FOR PERMIT AND THE |
| PLANS ALREADY STAMPED AS REVIEWED WILL BE DATE STAMPED |
| AND ISSUED WITH THE PERMIT. THREE SETS REQUIRED IF |
| SPECIAL INSPECTOR IS REQUIRED (SEE OTHER COMMENTS). |
| |
| SAME PLANS SUBMITTED. TWO ORIGINAL FINAL SETS OF PLANS |
| REQUIRED, FAC61G15-23. PLEASE REVISE PLANS AND SUBMIT |
| TWO SETS FOR PERMIT ISSUANCE. |
| |
| 3. PROVIDE THE ORIGINAL SOILS INVESTIGATION REPORT |
| REFERRED TO ON S0.0. |
| |
| 4. SPECIAL INSPECTOR REQUIRED PER SHEET S0.0. PLEASE |
| CONTACT KEN CONRAD, CHIEF BUILDING INSPECTOR REGARDING |
| THE SPECIAL INSPECTOR REQUIREMENTS. THIS PROCESS MUST |
| BE COMPLETED PRIOR TO PERMIT ISSUANCE. NOTE THAT THIS |
| IS A REQUIREMENT OF THE ENGINEER. ALTERNATIVELY, THE |
| REQUIREMENT MAY BE REMOVED FROM THE PLAN. |
| |
| 5. S0.0, GENERAL NOTE 2, PLEASE REVISE GOVERNING CODE |
| (FBC2007 WITH 2008 SUPPLEMENTS). |
| |
| 6. PLEASE PROVIDE A SITE PLAN SHOWING PROPOSED |
| LOCATION. |
| |
| |
| |
| |