2009-03-26 17:14:40 
  
 APPLICATION #09020479 ELECTRICAL PLAN REVIEW
 1025 OKEECHOBEE BLVD 3/26/09
 WEST PALM BEACH, FL.
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 2007 FBC AND REFERENCED STANDARDS THEREIN WILL
 BE THE GOVERNING CODE SINCE THE PROJECT WAS NOT IN
 APPLICATION STATUS UNTIL THAT CODE WAS ADOPTED. CHANGE
 ALL NOTES TO REFLECT THOSE CODES AT TIME OF
 APPLICATION.
  
 2} IF THERE IS TO BE ELECTRICAL INSTALLED FOR LIGHTING
 OR ANY PURPOSE A DISCONNECT WILL BE REQUIRED PER
 230.70(A)(1) AND MUST HAVE A GROUNDING ELECTRODE SYSTEM
 THAT WOULD INCLUDE BONDING TO BUILDING STEEL PER
 250.52(A)(3). SHOW ALL ELECTRICAL WIRING ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER