Plan Review Notes
Plan Review Notes For Permit 09020476
Permit Number 09020476
Review Stop ENG
Sequence Number 2
Notes
Date Text
2010-09-23 08:14:36FAIL STATUS:
  
 COMMENT #1
 - NO POLLUTION CONTROL PLAN SUBMITTED OR SUBMITTED WITH
 OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
 - SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO
 BE DISTURBED.
 - FILTER FABRIC IS REQUIRED UNDER THE CATCH BASIN
 GRATES WITH ROCK BAGS AT ANY CURBED INLET ON-SITE TO
 STOP SOLIDS FROM ENTER THE SYSTEM.
 - FILTER FABRIC IS REQUIRED UNDER THE CATCH BASIN
 GRATES WITH ROCK BAGS AT ANY CURBED INLET OFF-SITE TO
 STOP SOLIDS FROM ENTER THE SYSTEM.
 - ADD TURBIDITY BARRIER AT THE OUTFALL TO: (LIST THE
 CANAL OR AREA OF INTRACOASTAL THAT NEEDS PROTECTING.
 -SUPPLY POLLUTION CONTROL PLAN SHOWING:
 A) WHERE SILT SCREENS WILL BE INSTALLED,
 B) SHOW THE PROTECTION OF ALL ON-SITE CATCH BASINS
 C) SHOW PROTECTION OF ALL OFF-SITE CATCH BASINS
 D) INCLUDE DETAILS AS TO THE TYPE OF PROTECTION USED ON
 THE CATCH BASINS
 E) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS
 RUNOFF SHALL BE DISCHARGED FROM IMPERVIOUS SURFACES
 THROUGH RETENTION AREAS, DETENTION DEVICES, FILTERING
 AND CLEANSING DEVICES, OR SUBJECT TO SOME OTHER TYPE OF
 BEST MANAGEMENT PRACTICE (BMP) PRIOR TO DISCHARGE FROM
 THE PROJECT SITE. PROJECTS WHICH INCLUDE SUBSTANTIAL
 PAVED AREAS, SUCH AS, SHOPPING CENTERS, LARGE HIGHWAY
 INTERSECTIONS WITH FREQUENT STOPPED TRAFFIC, AND HIGH
 DENSITY DEVELOPMENTS, PROVISIONS SHALL BE MADE FOR THE
 REMOVAL OF OIL, GREASE, AND SEDIMENT FROM STORM WATER
 DISCHARGES.
  
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18), CHAPTER 90 UTILITIES,
 ARTICLE V. STORMWATER POLLUTION PREVENTION
 SEC. 90-203. PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A) GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES
  PERMIT, IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 DIRECTLY OR INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR
 DUMP INTO
  ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM
 SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER
  THAN THAT COMPOSED ENTIRELY OF STORM WATER.
  
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18), CHAPTER 94 ZONING AND LAND
 DEVELOPMENT REGULATIONS
 ARTICLE XIV. LANDSCAPING, LAND CLEARING, AND TREE
 PROTECTION
 SEC. 94-450. VACANT LOT AND CONSTRUCTION SITE
 MAINTENANCE.
 (A) INTENT. THE INTENT OF THIS SECTION IS TO MINIMIZE
 THE DETRIMENTAL HEALTH, SAFETY, GENERAL WELFARE AND
 IMPACTS OF VACANT
  LOTS AND CONSTRUCTION ACTIVITIES ON THE RESIDENTS OF
 THE CITY OF WEST PALM BEACH; TO ENSURE THAT EACH VACANT
 LOT AND
  CONSTRUCTION SITE IS MAINTAINED, AND EACH CONSTRUCTION
 ACTIVITY IS CONDUCTED IN SUCH A MANNER SO AS TO AVOID
  UNNECESSARY INCONVENIENCE AND ANNOYANCE TO THE GENERAL
 PUBLIC AND THE OCCUPANTS OF THE NEIGHBORING PROPERTIES;
  AND TO REQUIRE MAINTENANCE PRACTICES THAT WILL REDUCE
 THE AMOUNT OF SEDIMENT AND OTHER POLLUTANTS LEAVING
  CONSTRUCTION SITES DURING LAND DEVELOPMENT OR LAND
 DISTURBING CONSTRUCTION ACTIVITIES.
  
 COMMENT #2
 FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION (FDEP) -
 PROVIDE PROOF OF NOTICE OF INTENT.
 HTTP://EPIC229.DEP.STATE.FL.US/DWRMINOI/
 HTTP://WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
  
 NPDES STORM WATER NOTICES CENTER, MS# 2510
 FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION
 2600 BLAIR STONE ROAD
 TALLAHASSEE, FLORIDA 32399-2400
 PHONE (850) 245-7522
  
 NOTE: FDEP (PREVIOUSLY FLORIDA DEPARTMENT OF
 ENVIRONMENTAL REGULATION ??? FDER) HISTORICALLY HAS
 REGULATED DREDGE AND FILL OPERATIONS, AND STORM WATER
 DISCHARGE QUALITY UNDER CHAPTERS 62??302 (WATER
 QUALITY), 62-4 (PERMITS), 62-312 (DREDGE AND FILL),
 62-550 (DRINKING WATER), AND 62-25 (REGULATION OF STORM
 WATER DISCHARGE) OF THE FLORIDA ADMINISTRATIVE CODE
 (FAC). FDEP???S REGULATORY RESPONSIBILITIES HAVE GROWN
 SINCE THE ADOPTION OF THE FLORIDA AIR AND WATER
 POLLUTION CONTROL ACT. ADDITIONAL RESPONSIBILITIES
 ASSIGNED THROUGH THE NOVA CANAL SYSTEM WATERSHED STUDY
 AREA INCLUDE DESIGNATING AND ADMINISTERING OUTSTANDING
 FLORIDA WATERS (OFW) AND CLASS III SURFACE WATER
 QUALITY AREAS. FURTHERMORE, LEGISLATION HAS DEFINED
 DEP???S ROLE IN THE STATE NATIONAL POLLUTION DISCHARGE
 ELIMINATION SYSTEM (NPDES) PROGRAM, CREATION OF
 STORMWATER UTILITIES, AND WETLAND PROTECTION. DREDGE
 AND FILL ACTIVITIES WITHIN WETLANDS REQUIRE A PERMIT,
 EXCEPT FOR THOSE WHICH HAVE BEEN DELEGATED TO SFWMD.
  
 COMMENT#3
 PROJECT MUST MEET WATER QUALITY CRITERIA PER SFWMD
 (SOUTH FLORIDA WATER MANAGEMENT DISTRICT CRITERIA)
 RETENTION/DETENTION CALCULATIONS INCLUDING PERVIOUS AND
 IMPERVIOUS AREAS.
 SURFACE WATER CRITERIA:
 SFWMD, APPLICANTS TREAT FIRST INCH OF RUNOFF OR
 2 ?? TIMES THE IMPERVIOUS AREA, WHICH EVER IS GREATER.
 (ADDITIONAL 50% TREATMENT MUST BE PROVIDED FOR
 DISCHARGE INTO CLASS I AND II WATER BODIES.) (LITORAL
 ZONES OR CONSTRUCTED WETLANDS) (INCREASED CONTACT TIME
 WITH ???IN-WATER BAFFLE SYSTEMS OR INCREASED LAKES
 WIDTH AND TRAVEL DISTANCE.
 SUSPENTION OF SOLIDS IS ALSO A QUALITY ISSUE. REDUCE
 THE IMPACT OF NUTRIENT DISCHARGES FROM SURFACE WATER.
 WATER QUALITY.
 PRE ???VS- POST ANALYSIS DEMONSTRATING THAT THE
 PROPOSED POST-DEVELOPMENT DISCHARGE WILL BE NO GREATER
 THAN THE PRE-DEVELOPMENT (CURRENT CONDITION) DISCHARGE
 FOR THE PARAMETER THAT???S IMPAIRED.
  
 COMMENT #4
 ENGINEERING SERVICES EROSION CONTROL & LAND
 STABILIZATION BOND (ORD. 4060-07) *
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/UPLOADS/2009-06-16
 -14-38-16-PERFORMANCEBOND-IMPROVEMENTS.PDF
  
 COMMENT #5
 - NO SIDEWALK OR DRIVEWAY APPROACH PLAN SUBMITTED -
 ENGINEERING SERVICES DEPARTMENT APPROVAL.
 DRIVEWAY APPROACH CONFIGURATION, SITE CONSTRUCTION
 ACCESSIBILITY AND LOGISTICS PLAN SHOULD BE DISCUSSED
 WITH THE RIGHT-OF-WAY DIVISION PRIOR TO BEING SUBMITTED
 TO CONSTRUCTION SERVICES.
 MAINTENANCE OF TRAFFIC PLAN (M.O.T. PLAN) ??? IS
 REQUIRED TO ADDRESS SPECIFIC PLANS FOR LANE CLOSURES,
 DETOURS, OR OTHER IMPACTS ON OR AFFECTING STREETS AND
 ROADS UNDER THE JURISDICTION OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS, RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 CONTACT THE RIGHT-OF-WAY REVIEWER, WINDEL PALMER,
 PROJECT COORDINATOR, THE TRAFFIC ENGINEERS OFFICE AT:
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 401 - CLEMATIS, FOURTH FLOOR,
 WEST PALM BEACH FL 33401
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3366
 WEST PALM BEACH FL 33402
 TELEPHONES:
 MAIN OFFICE: 561-494-1040
 FAX: 561-494-1116
  
 COMMENT #6
 CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS AND
 PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE
 DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER
 UTILITIES WITHIN THE CITY OF WEST PALM BEACH.
 PLEASE SEE: DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS
 AT THE LINK BELOW:
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/UPLOADS/2010-08-24
 -14-41-27-DEVELOPMENTPERMITPACKAGE2010.PDF
  
 COMMENT #7
 PROVIDE ELEVATIONS AS IT RELATES TO NEW AND EXISTING
 BUILDINGS WHICH HAVE PLUMBING DRAIN OUTLETS AT AN
 ELEVATION 12??? OR LESS ABOVE THE GROUND SURFACE OF THE
 NEXT UPSTREAM
 MANHOLE, WHERE THE ELEVATION OF ANY FLOOR IS AT OR
 BELOW THE INVERT OF THE ADJACENT CITY SANITARY SEWER
 MAIN OR IS LESS THAN 12???ABOVE THE GROUND SURFACE OF
 THE NEXT UPSTREAM
 MANHOLE, OR WHERE A CONDITION EXISTS WHERE A PLUG IN
 THE CITY SANITARY SEWER MAIN WILL CAUSE THE HYDRAULIC
 GRADIENT TO RISE ABOVE THE LOWEST FLOOR LEVEL.
  
 COMMENT #8
 SUBMIT 3 COPIES OF APPROVED SITE PLAN.
  
 *******************************************************
 *************************
 CITY OF WPB ENGINEERING FORMS AND DESIGN REQUIREMENT
 INFORMATION
 CAN BE FOUND AT THE INTERNET LINK BELOW
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
 *******************************************************
 *************************
  
 FEEL FREE TO CONTACT ME IF ANY QUESTIONS OR CONCERNS,
 THANKS!
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  
  