Plan Review Notes For Permit 09020471 |
Permit Number |
09020471 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-03-09 10:04:48 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND | | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR | | DEFICIENCIES | | | | 2} 210.70(B)(B) FOR DWELLING UNITS, ATTACHED GARAGES, | | AND DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE | | WALL SWITCH???CONTROLLED LIGHTING OUTLET SHALL BE | | INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE | | OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. | | A VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS | | AN OUTDOOR ENTRANCE OR EXIT. | | | | 2} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE | | INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|