2009-03-30 14:33:59 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STA |
| |
| 1. TYPE IV CONSTRUCTION DECLARED; NOT CONSISTENT WITH |
| DETAILS. TYPE IV IS HEAVY TIMBER; PLEASE CLARIFY. |
| |
| 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| RECORD FBC*106. |
| |
| 3. PROVIDE ROOM DESIGNATIONS ON THE PLAN, FBC*106. |
| |
| 4. SHOW COMPLIANCE WITH FBC R704, INSPECTION FOR |
| TERMITES. |
| |
| 5. FBC R703.6.3, BOND BREAK REQUIRED, REVISE ALL |
| AFFECTED DETAILS. |
| |
| 6. ENERGY CALCS REQUIRED FBC 13-103. |
| |
| 7. ROOF PERMIT HAS BEEN APPLIED FOR. THEREFORE, ALL |
| ROOF PERMIT INFORMATION REQUIRED AT THIS TIME: |
| |
| A. INDICATE WHICH APPROVED ASSEMBLY IS TO BE INSTALLED |
| |
| B. PROVIDE ENHANCED FASTENING PATTERN FOR PERIMETER AND |
| CORNER ZONES |
| |
| 8. SHOW COMPLIANCE WITH FBC R401.3, DRAINAGE. |
| |
| 9. FBC R403.1.4, SHOW DISTANCE OF BOTTOM OF FOOTING TO |
| GRADE. |
| |
| 10. SHOW FINISHED FLOOR ELEVATION IN RELATION TO GRADE, |
| FBC*106. |
| |
| 11. SMOKE ALARMS REQUIRED, FBC R313.1. |
| |
| 12. ROOF SHEATHING NAILING NOT COMPLIANT WITH FBC R |
| 803.2.3.1. SEE DETAILS 1 A3, 2 A3, CHECK ALL. |
| |
| 13. DETAIL 4 A3 SPECIFIES 2X WALL STUDS, IN CONFLICT |
| WITH OTHER DETAILS, PLEASE CLARIFY DESIGN INTENT. |
| CALCULATIONS MAY BE REQUIRED. |
| |
| 14. DETAIL 4 A3 SPECIFIES "APPROVED HURRICANE STRAP," |
| PLEASE SPECIFY (BRAND, MODEL #). CHECK ALL DETAILS. |
| |
| 15. IMPACT FEES MAY BE DUE. PLEASE CONTACT PALM BEACH |
| COUNTY, 233-5025. |
| |
| 16. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| FOR THE WINDOW, FAC9B72. |
| |
| 17. IMPACT PROTECTION REQUIRED FOR THE NEW WINDOW, FBC |
| R301. |
| |
| |
| |
| |