 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER FLORIDA STATUTE 471.003 AN ENGINEER MUST DESIGN
 THIS SERVICE. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE. IN THIS CASE ENGINEERING IS REQUIRED
 BECAUSE THE SERVICE VOLTAGE IS OVER 240 VOLTS.
  
 2} PER ARTICLE 408.36(D)- SUPPLIED THROUGH A
 TRANSFORMER WHERE A PANELBOARD IS SUPPLIED THROUGH A
 TRANSFORMER, THE OVERCURRENT PROTECTION REQUIRED BY
 408.36(A), (B), AND (C) SHALL BE LOCATED ON THE
 SECONDARY SIDE OF THE TRANSFORMER.
  
 3} INDICATE THE RATING OF THE TRANSFORMER THAT IS
 INTENDED TO BE INSTALLED
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  