2009-02-24 09:57:382004 FBC W/2007 REVISIONS
 INSTALL (5) ACCORDION SHUTTERS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF SIGNED SEALED AND DATED
 COMPONENT AND CLADDING WINDLOAD CALCULATIONS FROM A
 FLORIDA LICENSED ENGINEER FOR THE ACCORDION SHUTTERS.
 FS471
  
 2) SUBMIT TWO COPIES OF THE OPENING PROTECTION
 INSTALLATION SCHEDULE.
  
 3) THE CONNECTION TYPE (A,D) THAT IS SPECIFIED ON THE
 SCHEDULE FOR OPENINGS 1 AND 3 WHICH HAVE WOOD
 SUBSTRATES ARE INCORRECT. MOUNTINGS 'A' AND 'D' REQUIRE
 POURED CONCRETE OR CONCRETE BLOCK SUBSTRATE. FOR WOOD
 SUBSTRATE SEE THE TABLES ON PAGES 16 AND 17 AND THE
 MOUNTINGS ON PAGES 18 AND 19 OF THE PRODUCT APPROVAL.
  
 4) SEE THE EDGE DISTANCE REQUIREMENTS FOR SPACING OF
 ANCHORS ON PAGE 14 OF THE PRODUCT APPROVAL. NOTE: THE
 ANCHOR SPACINGS IN THE TABLES ARE REQUIRED TO BE
 REDUCED FOR EDGE DISTANCES OF LESS THAN 3-1/2".
  
 5) THE SHUTTER SPAN SPECIFIED IN THE SCHEDULE FOR
 OPENINGS 2,4 AND 5 ARE MORE THAN 8', THEREFORE THE
 MAXIMUM SPAN OF 9' FROM THE TABLE ON PAGE 14 SHOULD BE
 USED. THIS WILL REQUIRE ANCHORS TO BE SPACED 7.5" FOR
 THE 'H' MOUNT AT THE FLOOR. PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW