Plan Review Notes For Permit 09020334 |
Permit Number |
09020334 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-03-04 14:36:27 | | | | | PROVISO | | | | 680.26(B) BONDED PARTS THE PARTS SPECIFIED IN | | 680.26(B)(1) THROUGH (B)(5) SHALL BE BONDED | | TOGETHER.THE METAL PARTS REQUIRED TO BE BONDED PER | | 680.26(B) INCLUDE ALL METAL PARTS OF ELECTRICAL | | EQUIPMENT ASSOCIATED WITH THE WATER-CIRCULATING SYSTEM | | OF THE POOL, ALL METAL PARTS OF THE POOL STRUCTURE, AND | | ALL FIXED METAL PARTS, WHICH INCLUDE CONDUIT AND | | PIPING, METAL DOOR FRAMES, AND METAL WINDOW FRAMES, | | WITHIN 5 FT OF THE INSIDE WALLS OF THE POOL AND NOT | | SEPARATED BY A PERMANENT BARRIER. THE BONDING OF THESE | | PARTS DOES NOT MEAN THEY ARE REQUIRED TO BE CONNECTED | | TO EACH OTHER; RATHER, IT MEANS THEY ARE REQUIRED TO BE | | CONNECTED TO A COMMON BONDING GRID BY USING AN | | INSULATED, COVERED, OR BARE SOLID COPPER CONDUCTOR NOT | | SMALLER THAN 8 AWG OR BY USING BRASS OR OTHER | | CORROSION-RESISTANT METAL CONDUIT. SEE EXHIBIT 680.11. | | CONNECTIONS ARE REQUIRED TO BE MADE BY EXOTHERMIC WELDS | | OR BY LISTED PRESSURE CONNECTORS, CLAMPS, OR OTHER | | LISTED MEANS, IN ACCORDANCE WITH 250.8. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | | | |
|