2009-03-04 14:36:27 
  
 PROVISO
  
 680.26(B) BONDED PARTS THE PARTS SPECIFIED IN
 680.26(B)(1) THROUGH (B)(5) SHALL BE BONDED
 TOGETHER.THE METAL PARTS REQUIRED TO BE BONDED PER
 680.26(B) INCLUDE ALL METAL PARTS OF ELECTRICAL
 EQUIPMENT ASSOCIATED WITH THE WATER-CIRCULATING SYSTEM
 OF THE POOL, ALL METAL PARTS OF THE POOL STRUCTURE, AND
 ALL FIXED METAL PARTS, WHICH INCLUDE CONDUIT AND
 PIPING, METAL DOOR FRAMES, AND METAL WINDOW FRAMES,
 WITHIN 5 FT OF THE INSIDE WALLS OF THE POOL AND NOT
 SEPARATED BY A PERMANENT BARRIER. THE BONDING OF THESE
 PARTS DOES NOT MEAN THEY ARE REQUIRED TO BE CONNECTED
 TO EACH OTHER; RATHER, IT MEANS THEY ARE REQUIRED TO BE
 CONNECTED TO A COMMON BONDING GRID BY USING AN
 INSULATED, COVERED, OR BARE SOLID COPPER CONDUCTOR NOT
 SMALLER THAN 8 AWG OR BY USING BRASS OR OTHER
 CORROSION-RESISTANT METAL CONDUIT. SEE EXHIBIT 680.11.
 CONNECTIONS ARE REQUIRED TO BE MADE BY EXOTHERMIC WELDS
 OR BY LISTED PRESSURE CONNECTORS, CLAMPS, OR OTHER
 LISTED MEANS, IN ACCORDANCE WITH 250.8.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER