2009-06-19 10:59:23 | BUILDING PLAN REVIEW |
| PERMIT: 09020290 |
| ADD: 1515 N FLAGLER DR 7TH FLOOR |
| CONT: LEIGHTON MCGINN |
| TEL: (561)951-0946 MARK ANDREWS |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| |
| PROVISO: |
| LEVEL 1 ALTERATION |
| |
| 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. THE ORIGINAL |
| BUILDING WAS DESIGNED UNDER A WIND ZONE OF 110 MPH, |
| FASTEST MILE, UNDER THE 2004 FBC THIS BUILDING IS |
| LOCATED IN A 140 MPH WIND ZONE, 3 SECOND GUST. THE 2007 |
| SUPPLEMENTS TAKES THE BUILDINGS EXPOSURE CATEGORY FROM |
| A ???B??? ZONE TO A ???C??? ZONE. THIS IS WHY WE HAVE |
| REQUEST THE FOLLOWING INFORMATION. |
| |
| |
| 2) MISSING WIND DESIGN INFORMATION. |
| 603.1.4 WIND DESIGN DATA. |
| |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF |
| WHETHER WIND LOADS GOVERN THE DESIGN OF THE |
| LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE |
| 6-1, ASCE 7 AND BUILDING CLASSIFICATION IN TABLE 1-1, |
| ASCE 7. |
| |
| 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND |
| APPLICABLE WIND DIRECTION SHALL BE INDICATED. |
| |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL |
| PRESSURE COEFFICIENT. |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE |
| USED FOR THE SELECTION OF EXTERIOR COMPONENTS AND |
| CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL. |
| |
| 3) SINCE THE INTENT IS TO REUSE THE EXISTING GLAZING |
| SYSTEM AND THE LOCATION OF THE GLAZING IS 60 FEET ABOVE |
| GRADE ONLY WIND PRESSURE NEEDS TO BE MET. THE ENGINEER |
| OF RECORD SHALL USE RATIONAL ANALYSIS TO VERIFY THAT |
| THE GLAZING SYSTEM CAPABILITY TO WITHSTAND THE HIGHER |
| WIND PRESSURES BOTH POSITIVE AND NEGATIVE BEFORE THE |
| FIRST INSPECTION. |
| |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |