2009-06-19 10:59:23BUILDING PLAN REVIEW
 PERMIT: 09020290
 ADD: 1515 N FLAGLER DR 7TH FLOOR
 CONT: LEIGHTON MCGINN
 TEL: (561)951-0946 MARK ANDREWS
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 PROVISO:
 LEVEL 1 ALTERATION
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THE ORIGINAL
 BUILDING WAS DESIGNED UNDER A WIND ZONE OF 110 MPH,
 FASTEST MILE, UNDER THE 2004 FBC THIS BUILDING IS
 LOCATED IN A 140 MPH WIND ZONE, 3 SECOND GUST. THE 2007
 SUPPLEMENTS TAKES THE BUILDINGS EXPOSURE CATEGORY FROM
 A ???B??? ZONE TO A ???C??? ZONE. THIS IS WHY WE HAVE
 REQUEST THE FOLLOWING INFORMATION.
  
  
 2) MISSING WIND DESIGN INFORMATION.
 603.1.4 WIND DESIGN DATA.
  
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE
 LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE
 6-1, ASCE 7 AND BUILDING CLASSIFICATION IN TABLE 1-1,
 ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL
 PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE
 USED FOR THE SELECTION OF EXTERIOR COMPONENTS AND
 CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 3) SINCE THE INTENT IS TO REUSE THE EXISTING GLAZING
 SYSTEM AND THE LOCATION OF THE GLAZING IS 60 FEET ABOVE
 GRADE ONLY WIND PRESSURE NEEDS TO BE MET. THE ENGINEER
 OF RECORD SHALL USE RATIONAL ANALYSIS TO VERIFY THAT
 THE GLAZING SYSTEM CAPABILITY TO WITHSTAND THE HIGHER
 WIND PRESSURES BOTH POSITIVE AND NEGATIVE BEFORE THE
 FIRST INSPECTION.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved