2009-04-24 11:06:43 | BUILDING PLAN REVIEW |
| PERMIT: 09020290 |
| ADD: 1515 N FLAGLER DR 7TH FLOOR |
| CONT: LEIGHTON MCGINN |
| TEL: (561)951-0946 MARK ANDREWS |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 2) MISSING WIND DESIGN INFORMATION. |
| 603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| 3) PLANS DO NOT INDICATE THE WORK BEING COVERED UNDER |
| THE 2004 EXISTING BUILDING CODE NOR LEVEL OF ALTERATION |
| PER 2004 EXISTING BUILDING CODE 301.5 ADESSIGN |
| PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| COMBINATION OF LEVELS OF ALTERATION PURSUANT TO SECTION |
| 303,304 AND 305 OF THIS CODE. |
| |
| 4) MISSING INFORMATION: 2004 EXISTING BUILDING CODE - |
| LEVEL ONE -507.3. REPLACEMENT OF WINDOWS AND DOORS. |
| THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS, |
| SKYLIGHT, OPERATIVE AND INOPERATIVE WINDOWS SHALL BE |
| DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF |
| THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 5) MISSING WINDOW INFORMATION : 1609.1.4 PROTECTION OF |
| OPENINGS. |
| IN WIND-BORNE DEBRIS REGIONS, GLAZING IN BUILDINGS |
| SHALL BE IMPACT RESISTANT OR PROTECTED WITH AN IMPACT |
| RESISTANT COVERING MEETING THE REQUIREMENTS OF SSTD 12, |
| ASTM E 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE |
| DOORS AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND |
| 203 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS: |
| 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF |
| GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| TEST. |
| 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| |
| FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| COPIES, |
| 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| FIXED GLAZING. |
| |
| PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 5) THRESHOLD BUILDING: |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 5A)109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| 5B)THRESHOLD INSPECTOR: |
| WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| CODE. |
| CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 5C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| 6) ADDITIONAL INFORMATION IS REQUIRED, PICTURES TAKEN |
| WHEN THE OPENING WAS CREATED INDICATES THE USE OF |
| SCAFFOLDING THE FLOOR BELOW FOR THE LENGTH OF THE |
| BUILDING WHERE CT SCANNER AND VARIOUS MRI UNITS ARE |
| PLACED, PLEASE PROVIDE AN EXPLANATION, HAVE THE SAFE |
| LIVE AND DEAD FLOOR LOADS BEEN EXCEDED? THESE FLOORS |
| WOULD OF BEEN DESIGNED AS OFFICES WITH A SAFE LIVE LOAD |
| OF 50 OR A CONCENTRATED LOAD OF 2,000 PSF OVER A 2.5 |
| TRIBUTARY AREA. TABLE 1607.1 LIVE LOADS AND 1607.3 LIVE |
| LOADS & 1607.4 CONCENTRATED LOADS. |
| |
| 7) DETAIL SHEET FROM ALBERT A. GARGIULO P. E. ONLY ONE |
| OF THE THREE DETAILED SHEETS ARE RAISED SEAL ORIGINAL |
| SIGNATURE, THEY ARE COPIES. |
| |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| |
| 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED |
| BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: |
| NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, |
| THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| IS PRACTICING (471.025 F.S. AND 471.023 F.S.). |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |