2009-02-17 10:25:38 | DENIED |
| REFERENCE: |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS |
| PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. -- THE DROP FROM METER & THE OFFSET TO |
| FUTURE GAS AND RISER AT END OF RUN LENGHTS ARE NOT |
| INDICATED. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. -- THE RISER AND |
| THE DROP TO NEW DRYER NOT INDICATED. (CSST OR GALV.) |
| |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). -- BTU LOAD FOR THE FUTURE AT THE END OF THE |
| LINE IS NOT INDICATED. |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). -- INDICATE THE DISTANCE |
| FROM THE REGULATOR TO THE MOST REMOTE FOR THE W/H & |
| DRYER. |
| |
| 5. THE PRESSURE IS INDICATED AS 2 PSI, BUT NO |
| REGULATORS ARE INDICATED FOR THE POOL HEATER NOR FOR |
| THE FUTURE AT THE END OF THE LINE. PLEASE SHOW REQUIRED |
| REGULATORS ON THE ISOMETRIC. A SHUT OFF VALVE IS |
| REQUIRED PRIOR TO THE REGULATORS WITH A UNION |
| DOWNSTREAM OF THE SHUT OFF VALVE FOR THE DRYER & WATER |
| HEATER. SECTIONS 409.4 & 410.1. |
| |
| 6. SUBMIT THE REGULATOR MANUFACTURE SPECIFICATION & |
| MODEL NUMBER WITH INSTALLATION INSTRUCTIONS OR INDICATE |
| THE MANUF. AND MODEL NUMBER ON THE RISER DIAGRAM FOR |
| EACH REGULATOR. SECTIONS 106.1.2 & 410.1. |
| |
| 7. THE PERSON RESPONSIBLE FOR THE DESIGN OF THE GAS |
| RISER SHALL PRINT THEIR NAME AND AFFIX THEIR SIGNATURE |
| ON THE PLANS. SECTION 106.1.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |