2009-02-17 10:25:38DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- THE DROP FROM METER & THE OFFSET TO
 FUTURE GAS AND RISER AT END OF RUN LENGHTS ARE NOT
 INDICATED.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- THE RISER AND
 THE DROP TO NEW DRYER NOT INDICATED. (CSST OR GALV.)
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). -- BTU LOAD FOR THE FUTURE AT THE END OF THE
 LINE IS NOT INDICATED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- INDICATE THE DISTANCE
 FROM THE REGULATOR TO THE MOST REMOTE FOR THE W/H &
 DRYER.
  
 5. THE PRESSURE IS INDICATED AS 2 PSI, BUT NO
 REGULATORS ARE INDICATED FOR THE POOL HEATER NOR FOR
 THE FUTURE AT THE END OF THE LINE. PLEASE SHOW REQUIRED
 REGULATORS ON THE ISOMETRIC. A SHUT OFF VALVE IS
 REQUIRED PRIOR TO THE REGULATORS WITH A UNION
 DOWNSTREAM OF THE SHUT OFF VALVE FOR THE DRYER & WATER
 HEATER. SECTIONS 409.4 & 410.1.
  
 6. SUBMIT THE REGULATOR MANUFACTURE SPECIFICATION &
 MODEL NUMBER WITH INSTALLATION INSTRUCTIONS OR INDICATE
 THE MANUF. AND MODEL NUMBER ON THE RISER DIAGRAM FOR
 EACH REGULATOR. SECTIONS 106.1.2 & 410.1.
  
 7. THE PERSON RESPONSIBLE FOR THE DESIGN OF THE GAS
 RISER SHALL PRINT THEIR NAME AND AFFIX THEIR SIGNATURE
 ON THE PLANS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  