Plan Review Notes
Plan Review Notes For Permit 09020255
Permit Number 09020255
Review Stop E
Sequence Number 2
Notes
Date Text
2009-05-29 16:18:12*** DENIED 2ND REVIEW ****
  
 ** SOME OF THE EXACT SAME NOTES FROM PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM
 BUILDING REVIEWER ALSO. THE ENGINEERING LETTER ATTACHED
 TO PLANS FROM IETS DOES NOT CONTAIN AN ORIGINAL
 SIGNATURE. IT IS IN FACT A RUBBER STAMP SIGNATURE. THIS
 IS NOT PERMITTED UNDER FS 471.025. THIS CAN BE
 CONFIRMED WITH THE FLORIDA BOARD OF ENGINEERS. THIS WAS
 NOTED EXACTLY AS PER PREVIOUS REVIEW YET THE SAME
 LETTER WITH THE SAME RUBBER STAMP ON EACH WAS SUBMITTED
 BACK.
 ORIGINAL SIGNATURE IS REQUIRED, FAC 61G15-23.002,
 FS471.025
  
 2) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM
 BUILDING REVIEWER. THE DOCUMENTS ATTACHED FOR
 ENGINEERED ENDEAVORS INC ARE SEALED WITH A RAISED SEAL
 WHICH IS NO LONGER IN USE IN THE STATE OF FLORIDA. THE
 SAID SEAL FOR MR. MICHAEL MOREL HAS NOT BEEN VALID FOR
 SEVERAL YEARS. FAC 61G15-23.002 RULING WAS REVISED IN
 FEBRUARY OF 2004 WHICH REQUIRED THE SEAL TO BE REVISED
 TO CONTAIN THE WORDING OF LICENSE INSTEAD OF
 *CERTIFICATE*. AN EXTENSION WAS GIVEN TO DECEMBER 31ST,
 2005 HOWEVER ALL OLD SEALS AFTER SUCH DATE WERE NO
 LONGER PERMITTED TO BE USED IN THE STATE OF FLORIDA.
 NEW SEAL NEEDS TO BE OBTAINED.
 ** THIS IS ONLY NOTED BY THIS REVIEWER TO GIVE
 INFORMATION AHEAD OF TIME. THIS MAY HELP TO ALLEVIATE
 FURTHER DELAYS.
  
 3) NOTE: AS NOTED ON PREVIOUS REVIEW. THE SEAL ON THE
 ELECTRICAL PLANS ARE NOT CLEAR AND VISIBLE. EVEN USE OF
 LEAD RUB DOES NOT IDENTIFY THE REQUIRED INFORMATION ON
 SAID SEAL. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002, .001 AND FLORIDA STATUTES 471.025. ALL
 INFORMATION ON SEALS NEEDS TO BE CLEAR AND VISIBLE.
 **ENGINEER MAY RE-SEAL PLANS, SIGN AND DATE IN THIS
 OFFICE IF THIS WOULD HELP WITH THE PROJECT. THE SEAL
 MUST HAVE ALL INFORMATION CLEAR AND VISIBLE. OBTAIN NEW
 SEAL IF IT CAN BE READ.
  
 4) NOTE: THIS WAS NOTED ON PREVIOUS REVIEW. THERE ARE
 NOW TWO TRANSFER SWITCHES SHOWN ON PLANS. PLEASE SUBMIT
 THE MANUFACTURES SPECS/CUT SHEETS FOR ANY PROPOSED
 TRANSFER SWITCH AUTOMATIC, MANUAL, LEGALLY REQUIRED OR
 OPTIONAL STAND-BY.
 90.7, 110.3, 701.7, 702.6. NO REVIEW CAN BE DONE AT
 THIS TIME FOR THSE ITEMS.
 ** THE GENERATOR SPECS/CUT SHEETS ARE THE ONLY RELEVANT
 SPECS IN SETS. (ATTACHED TO FRONT)
  
  
  
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  