Date |
Text |
2009-05-29 16:18:12 | *** DENIED 2ND REVIEW **** |
| |
| ** SOME OF THE EXACT SAME NOTES FROM PREVIOUS REVIEW |
| STILL NEED TO BE ADDRESSED. |
| |
| 1) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM |
| BUILDING REVIEWER ALSO. THE ENGINEERING LETTER ATTACHED |
| TO PLANS FROM IETS DOES NOT CONTAIN AN ORIGINAL |
| SIGNATURE. IT IS IN FACT A RUBBER STAMP SIGNATURE. THIS |
| IS NOT PERMITTED UNDER FS 471.025. THIS CAN BE |
| CONFIRMED WITH THE FLORIDA BOARD OF ENGINEERS. THIS WAS |
| NOTED EXACTLY AS PER PREVIOUS REVIEW YET THE SAME |
| LETTER WITH THE SAME RUBBER STAMP ON EACH WAS SUBMITTED |
| BACK. |
| ORIGINAL SIGNATURE IS REQUIRED, FAC 61G15-23.002, |
| FS471.025 |
| |
| 2) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM |
| BUILDING REVIEWER. THE DOCUMENTS ATTACHED FOR |
| ENGINEERED ENDEAVORS INC ARE SEALED WITH A RAISED SEAL |
| WHICH IS NO LONGER IN USE IN THE STATE OF FLORIDA. THE |
| SAID SEAL FOR MR. MICHAEL MOREL HAS NOT BEEN VALID FOR |
| SEVERAL YEARS. FAC 61G15-23.002 RULING WAS REVISED IN |
| FEBRUARY OF 2004 WHICH REQUIRED THE SEAL TO BE REVISED |
| TO CONTAIN THE WORDING OF LICENSE INSTEAD OF |
| *CERTIFICATE*. AN EXTENSION WAS GIVEN TO DECEMBER 31ST, |
| 2005 HOWEVER ALL OLD SEALS AFTER SUCH DATE WERE NO |
| LONGER PERMITTED TO BE USED IN THE STATE OF FLORIDA. |
| NEW SEAL NEEDS TO BE OBTAINED. |
| ** THIS IS ONLY NOTED BY THIS REVIEWER TO GIVE |
| INFORMATION AHEAD OF TIME. THIS MAY HELP TO ALLEVIATE |
| FURTHER DELAYS. |
| |
| 3) NOTE: AS NOTED ON PREVIOUS REVIEW. THE SEAL ON THE |
| ELECTRICAL PLANS ARE NOT CLEAR AND VISIBLE. EVEN USE OF |
| LEAD RUB DOES NOT IDENTIFY THE REQUIRED INFORMATION ON |
| SAID SEAL. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.002, .001 AND FLORIDA STATUTES 471.025. ALL |
| INFORMATION ON SEALS NEEDS TO BE CLEAR AND VISIBLE. |
| **ENGINEER MAY RE-SEAL PLANS, SIGN AND DATE IN THIS |
| OFFICE IF THIS WOULD HELP WITH THE PROJECT. THE SEAL |
| MUST HAVE ALL INFORMATION CLEAR AND VISIBLE. OBTAIN NEW |
| SEAL IF IT CAN BE READ. |
| |
| 4) NOTE: THIS WAS NOTED ON PREVIOUS REVIEW. THERE ARE |
| NOW TWO TRANSFER SWITCHES SHOWN ON PLANS. PLEASE SUBMIT |
| THE MANUFACTURES SPECS/CUT SHEETS FOR ANY PROPOSED |
| TRANSFER SWITCH AUTOMATIC, MANUAL, LEGALLY REQUIRED OR |
| OPTIONAL STAND-BY. |
| 90.7, 110.3, 701.7, 702.6. NO REVIEW CAN BE DONE AT |
| THIS TIME FOR THSE ITEMS. |
| ** THE GENERATOR SPECS/CUT SHEETS ARE THE ONLY RELEVANT |
| SPECS IN SETS. (ATTACHED TO FRONT) |
| |
| |
| |
| |
| * IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |