Date |
Text |
2009-03-18 12:04:31 | DENIED |
| REFERENCE: |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. -- THE ISOMETRIC AS SHOWN DOES NOT SHOW |
| ANY PIPING UNDERGROUND. THE PIPING TO THE METER AND OUT |
| OF THE METER DOES NOT DROP DOWN FROM THE METER NOR DOES |
| IT RISE UP TO THE METER ON THE SUPPLY SIDE. PLEASE |
| CLARIFY. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. -- NOTE ON SHT 1 |
| OF 1 NG GENERATOR INSTALLATION STATES, "3/4" BLACK IRON |
| PIPE SUITABLE FOR NATURAL GAS ABOVE GROUND TO BE ROUTED |
| TO 3/4" POLYETHELENE FROM THE TANK TO THE GENERATOR |
| WITH A MINIMU 12-INCHES OF COVER". PLEASE INDICATE WHAT |
| TANK. PLEASE SEE COMMENT #1 AS THE ISOMETRIC DOES NOT |
| SHOW THE PIPING UNDERGROUND, OR IF PIPING IS SHOWN |
| UNDERGROUND, THEN THE METER IS INDICATED BELOW GROUND. |
| PLEASE CLARIFY. |
| |
| 3. ALL SHEETS, THE PROJECT DATA SHALL INCLUDE THE |
| FBC-2004 WITH 2007 SUPPLEMENTS. SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |