Plan Review Notes
Plan Review Notes For Permit 09020255
Permit Number 09020255
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-04-01 15:15:09***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2006. SHT 2
 OF 8
  
 2) GENERATOR AND ASSOCIATED EQUIPMENT MAY REQUIRE
 PROTECTION AGAINST THE POSSIBILITY OF MECHANICAL
 DAMAGE.
  
 3) WHAT IS THE LOCATION OF REFERENCED EQUIPMENT
 RELATIVE TO NEARBY STRUCTURES?
  
 4) GENERATOR TO COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS.
  
 5) PROVIDE INFORMATION EXPLAINING THE PURPOSE OF THE
 GENERATOR. THE SCOPE OF WORK APPEARS SOMEWHAT
 CONFUSING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756