2009-03-16 09:37:46 | ** DENIED ** |
| |
| |
| 1) NOTE: ENGINEERING LETTER ATTACHED TO PLANS FROM IETS |
| DOES NOT CONTAIN AN ORIGINAL SIGNATURE. IT IS IN FACT A |
| RUBBER STAMP SIGNATURE. THIS IS NOT PERMITTED UNDER FS |
| 471.025. THIS CAN BE CONFIRMED WITH THE FLORIDA BOARD |
| OF ENGINEERS. |
| PLEASE USE ORIGINAL SIGNATURES EVEN IF COMMENT IS NOT |
| MADE BY OTHER TRADES. |
| |
| 2) NOTE: PLEASE PROVIDE COMPLETE DOCUMENTATION ON THE |
| TYPE OF GENERATOR SYSTEM BEING INSTALLED. IS THIS A |
| LEGALLY REQUIRED SYSTEM? PLEASE SEE 701.11B3. ON SITE |
| FUEL IS REQUIRED MEETING MINIMUM TIMES. |
| PLEASE SEE FEDERAL CODE OF REGULATIONS TITLE 47 PART 12 |
| FOR UPDATES OF SYSTEMS FOR CELL TOWER POWER BACK UP. |
| THIS INCLUDES ANY 911 OR E911 SYSTEMS. |
| SHEET 4 OF THE SET MENTIONS POSSIBLE BATTERY CABINETS |
| HOWEVER THIS WAS NOT LOCATED ON ELECTRICAL SHEETS. ARE |
| THERE BATTERY CABINETS PROVIDING 8HRS BACK UP AND THE |
| GENERATOR IS IN ADDITION TO THIS? IS THERE NOT GOING TO |
| BE ANY GENERATOR AND ONLY BATTERY? SEE NOTE #4 BELOW. |
| |
| 3) NOTE: THE FOLLOWING CODES NEED TO BE STATED ON |
| ELECTRICAL PLANS. |
| 2005 NFPA-70. |
| |
| 4) NOTE: THERE IS CONFUSION OVER WHAT SCOPE OF WORK IS |
| BEING APPLIED FOR: THE PERMIT APPLICATION MENTIONS THE |
| INSTALLATION OF A PERMANENT GENERATOR, ALONG WITH |
| ATTACHED SPECS/CUT SHEETS, AND THE GAS PLAN. HOWEVER |
| THE ELECTRICAL PLANS INDICATES A MANUAL TRANSFER SWITCH |
| WITH A RECEPTACLE FOR A PORTABLE GENERATOR. THE |
| ELECTRICAL RISER INDICATES POSSIBLY BATTERY CABINET OR |
| GENERATOR. THE PROPOSED SCOPE OF WORK NEEDS TO BE |
| SPECIFIC TO THE LOCATION. THERE ARE TOO MANY UNKNOWNS |
| AT THIS TIME FOR THE WORK. |
| FBC 106.1.1, 106.1.2, 106.3.5.1.2, 106.5. ( |
| ADMINISTRATIVE SECTIONS FOR ADDITIONAL INFORMATION, |
| CLARITY AND COORDINATION OF PLANS. |
| NEC 2005 ALL CHAPTERS AS APPLICABLE AS THE SCOPE IS NOT |
| CLEAR. ALSO SEE NOTES #2 ABOVE. |
| |
| 5) NOTE: THE SEAL ON THE ELECTRICAL PLANS ARE NOT CLEAR |
| AND VISIBLE. EVEN USE OF LEAD RUB DOES NOT IDENTIFY THE |
| REQUIRED INFORMATION ON SAID SEAL. PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002, .001 AND FLORIDA |
| STATUTES 471.025. ALL INFORMATION ON SEALS NEEDS TO BE |
| CLEAR AND VISIBLE. |
| |
| 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| SHEETS FOR ANY PROPOSED TRANSFER SWITCH AUTOMATIC, |
| MANUAL, LEGALLY REQUIRED OR OPTIONAL STAND-BY. |
| 90.7, 110.3, 701.7, 702.6 |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |