Date |
Text |
2009-03-09 16:58:22 | BUILDING PLAN REVIEW |
| PERMIT: 09020255 |
| ADD: 1750 FLORIDA MANGO RD |
| CONT: CARRICK CONSTRUCTION |
| TEL: (954)415-5705 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE |
| UPDATE PLANS SHEET 6 OF 8 AND SHEET# 1 OF STRUCTURAL |
| CALCULATIONS. |
| |
| 2) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF |
| ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE |
| REQUIRED. PLEASE PROVIDE AT WHAT ELEVATION THE SLAB |
| WILL BE SET, THE FLOODZONE A9- MINIMUM ELEVATION 13.5 |
| FT. |
| |
| 3A) 106.1.2 ADDITIONAL INFORMATION REQUIRED IETS |
| STRUCTURAL REPORT INDICATES ON SHEET E-1 WHAT APPEARS |
| TO BE THE TOP CONNECTION (SECTION) OF TOWER. THIS |
| SECTION IS LOCATED AT HEIGHT 108.8' AND CONTINUES |
| THROUGH TO 128.8'. THE PERMIT APPLICATION INDICATES |
| ONLY A TEN FOOT SECTION IS BEING ADDED FROM 113' TO |
| 123'. PLEASE EXPLAIN THE DIFFERENCE. |
| |
| 3B) THE IETS CALCULATIONS DO NOT INDICATE HOW THE TOP |
| SECTION OF TOWER WILL BE ATTACHED NOR IS THERE ANY |
| INFORMATION AS TO THE CONFIGURATION, TYPE OF MATERIAL |
| NOR THICKNESS OF MATERIAL THIS NEW TOWER SECTION WILL |
| BE CONSTRUCTED FROM, 106.1.2 ADDITIONAL INFORMATION/ |
| 1609.6.2.1 MAIN WINDFORCE-RESISTING SYSTEM. |
| |
| 3C) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE |
| OF CONNECTION THE NEW SECTION OF THE TOWER WILL CONSIST |
| OF, 106.1.2 ADDITIONAL INFORMATION. PLEASE ALSO PROVIDE |
| WHERE THIS ANYLISS WOULD BE FOUND WITHIN YOUR DOCUMENT? |
| 106.1.2 ADDITIONAL INFORMATION/ 1609.6.2.1 MAIN |
| WINDFORCE-RESISTING SYSTEM. |
| |
| 4) IETS COVER-SHEET; |
| 4A) THE REPORT HAS PHOTOCOPIED SIGNATURES, NOT |
| ORIGINALS, FL ADMINISTRATIVE CODE: 61G15-23.002(2) FL. |
| ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL |
| ENGINEER. |
| (471.025 F.S. AND 471.023 F.S.). |
| |
| 4B) 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR |
| INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED |
| AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF |
| THE PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| ON THE COVER SHEET OR INDEX. |
| |
| 4C) 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE |
| TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN |
| ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |