Plan Review Notes For Permit 09020237 |
Permit Number |
09020237 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-02-12 11:23:29 | 2004 FBC W/2007 REVISIONS | | RE-ROOF | | | | DENIED BY BUILDING | | | | 1) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF SYSTEM | | THAT WILL BE USED. DCA RULE 9B-72. | | | | 2) SPECIFY THE APPROVED SYSTEM, FASTENING OPTION AND | | DESIGN PRESSURE FOR THE FLAT ROOF SYSTEM THAT WILL BE | | INSTALLED. CIRCLE THE APPROPRIATE INFORMATION ON THE | | PRODUCT APPROVAL. | | | | 3) SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING | | AT THE PERIMETER AND CORNER AREAS IF REQUIRED. SIGNED | | AND SEALED CALCULATIONS WILL BE REQUIRED IF PRODUCT | | APPROVAL LIMITATIONS SPECIFY THEM. | | | | 4) THE VALUE OF THE WORK IS TOO LOW AND HAS BEEN | | ADJUSTED TO $6429.00 BASED ON MARSHALL AND SWIFT | | VALUATION. ADDITIONAL PERMIT FEES OF $79.84 ARE DUE. | | FBC 108.3* CITY AMENDMENTS. | | | | 5) DUE TO THE INCREASE IN VALUE A NOTICE OF | | COMMENCEMENT WILL BE REQUIRED. FS 713 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|