Plan Review Notes
Plan Review Notes For Permit 09020219
Permit Number 09020219
Review Stop ENG
Sequence Number 4
Notes
Date Text
2009-07-27 09:44:21PASSED WITH PROVISOS:
 I DO NOT KNOW WHY THESE COMMENTS HAVE NOT BEEN
 ADDRESSED ALREADY, BUT THESE COMMENTS WERE GIVEN TO THE
 CIVIL ENGINEER.
 SHEET C-5:
 1. WATER SERVICES ARE NOT TO BE BUILT AS SHOWN IN THIS
 DETAIL. THE SERVICES WILL BE BUILT ACCORDING TO DETAIL
 WS-1 ON SHEET C7.
 2. A 3/4" METER WILL NOT GIVE THE REQUIRED FLOWS NEEDED
 FOR AN IRRIGATION METER. EITHER REDESIGN THE IRRIGATION
 SYSTEM, OR CHANGE THE DRAWING TO SHOW A 2" WATER
 SERVICE WITH A 1-1/2" IRRIGATION METER. A 3/4" METER
 WILL ONLY GIVE YOU 15 GPM AT A MAXIMUM CONTINUOUS FLOW
 RATE. A 1" METER WILL ONLY GIVE YOU 25 GPM MAX. CON.
 RATE. YOUR IRRIGATION PLANS SHOW 2 ZONES OVER 25 GPM,
 WHICH EXCEEDS A 1" METER, 10 OF THE ZONES EXCEEDS THE
 15 GPM RATE OF A 3/4" METER.
 3. THE STREET LIGHT POLE IS DESIGNATED TO BE RELOCATED
 BY OTHERS, THE OTHERS IS NOT THE CITY OF WEST PALM
 BEACH. IF THE LIGHT POLE IS IN THE WAY OF THE PROPOSED
 DRIVEWAY IT IS THE DEVELOPERS RESPONSIBILITY TO HAVE IT
 RELOCATED.
  