Date Text
2009-02-13 17:37:31DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS L-3, L-4 & L-5 THE ADDRESS OF RECORD OF THE
 DESIGN PROFESSIONAL ON THE FLORIDA STATE DBPR WEBSITE,
 (10748 DEERWOOD PARK BLVD. SOUTH JACKSONVILLE, FL) DOES
 NOT REFLECT THE ADDRESS INDICATED ON THE TITLE BLOCKS,
 (1715 N. WESTSHORE BLVD. TAMPA FLORIDA). FAC
 61G1-16.004(1) & FS 481.306. PLEASE UPDATE THE TITLE
 BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING PLANS
 FOR REVIEW.
  
 1. SHT L-3 PLEASE INDICATE THE LOCATION OF THE BACKFLOW
 PREVENTER AND THE RAIN SENSOR ON THE IRRIGATION PLAN.
 SECTIONS 106.1.2 AND APPENDIX F(J) AS WELL AS FS
 3373.62. PLEASE INDICATE IF THERE WILL BE A SEPARATE
 METER FOR THE IRRIGATION. IF CONNECTING TO THE WATER
 SERVICE FOR THE BUILDING, THEN A REDUCED PRESSURE
 BACKFLOW CAN BE USED. TABLE 608.1. (SEE CIVIL SHEET C7
 UTILITY DETAIL
  
 3. SHT L-4 DETAIL 5/L-04 DOUBLE CHECK ASSEMBLY IS NOT
 APPROVED. AN RPZV BACKFLOW PREVENTOR IS REQUIRED.
 SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  