2009-02-13 17:37:31 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHTS L-3, L-4 & L-5 THE ADDRESS OF RECORD OF THE |
| DESIGN PROFESSIONAL ON THE FLORIDA STATE DBPR WEBSITE, |
| (10748 DEERWOOD PARK BLVD. SOUTH JACKSONVILLE, FL) DOES |
| NOT REFLECT THE ADDRESS INDICATED ON THE TITLE BLOCKS, |
| (1715 N. WESTSHORE BLVD. TAMPA FLORIDA). FAC |
| 61G1-16.004(1) & FS 481.306. PLEASE UPDATE THE TITLE |
| BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING PLANS |
| FOR REVIEW. |
| |
| 1. SHT L-3 PLEASE INDICATE THE LOCATION OF THE BACKFLOW |
| PREVENTER AND THE RAIN SENSOR ON THE IRRIGATION PLAN. |
| SECTIONS 106.1.2 AND APPENDIX F(J) AS WELL AS FS |
| 3373.62. PLEASE INDICATE IF THERE WILL BE A SEPARATE |
| METER FOR THE IRRIGATION. IF CONNECTING TO THE WATER |
| SERVICE FOR THE BUILDING, THEN A REDUCED PRESSURE |
| BACKFLOW CAN BE USED. TABLE 608.1. (SEE CIVIL SHEET C7 |
| UTILITY DETAIL |
| |
| 3. SHT L-4 DETAIL 5/L-04 DOUBLE CHECK ASSEMBLY IS NOT |
| APPROVED. AN RPZV BACKFLOW PREVENTOR IS REQUIRED. |
| SECTION 608.13.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |
| |
| |
| |
| |