2009-03-10 10:51:20 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| REVISIONS. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 2- REVISE ENERGY CALCULATIONS: |
| A) NEED TO USE REVISED FORM 600C-04R. FORM SUBMITTED IS |
| NOT THE REVISED ONE. |
| |
| B) COMPLETE ALL INFORMATION ON TOP OF FORM INCLUDING |
| PERMITTING OFFICE (CITY OF WEST PALM BEACH) AND |
| JURISDICTION # (604700). |
| |
| C) COMPLETE ITEM #2. |
| |
| D) REVISE ITEM #10A. MIN. UNDER ATTIC INSULATION IS |
| R-30 AS REQUIRED BY TABLE 6C-1 ON SECOND PAGE OF ENERGY |
| CALCULATIONS. |
| |
| E) COMPLETE INFORMATION ON TABLE 6C-2 ON SECOND PAGE OF |
| ENERGY CALCULATIONS. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR WINDOW MULLIONS AS SHOWN ON PLANS. |
| **NOTE: CLEARLY SPECIFY ON PRODUCT APPROVAL MULLION |
| SIZE AND ANCHORING TO VERIFY COMPLIANCE WITH THE |
| CALCULATED DESIGN PRESSURES. |
| |
| 4- ENGINEER OF RECORD TO REVIEW AND APPROVED IN WRITING |
| MULLION PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 5- ENGINEER TO PROVIDE HIS LICENSE NUMBER IN ALL SHEETS |
| TITLE BLOCK AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA |
| ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| |
| 6- ENGINEERING DRAWING SHEET #2: |
| A) REVISE DESIGN CRITERIA: THIS IS THE CITY OF WEST |
| PALM BEACH JURISDICTION NOT CITY OF PORT ST. LUCIE. |
| |
| B) UPDATE INFORMATION REFER TO FBC 2004 WITH 2007 |
| REVISIONS, NOT 2006. |
| |
| C) ENGINEER SPECIFIES IMPACT RESISTANT ASSEMBLY FOR |
| COMPONENTS AND CLADDING. PRODUCT APPROVALS SUBMITTED |
| FOR FRENCH DOORS AND FIXED WINDOWS ARE FOR NON-IMPACT |
| ASSEMBLIES. SPECIFY HOW COMPLYING WITH THE GLASS IMPACT |
| PROTECTION OF SEC. R301.2.1.2 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| ***NOTE: IF USING ANY TYPE SHUTTERS FOR IMPACT |
| PROTECTION, THEN PROVIDE COMPLETE INSTALLATION SCHEDULE |
| (SEE ATTACHED SAMPLE) AND PROVIDE PRODUCT APPROVALS |
| REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. |
| |
| D) CLARIFY WHY NOT SPECIFYING VERTICAL REINFORCEMENT AT |
| EACH END OF DOUBLE WINDOW OPENING TO VERIFY COMPLIANCE |
| WITH SEC. R606 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |