2009-05-04 13:12:25PASSED WITH PROVISOS:
 EMAIL: [email protected]
 OFFICE: 561-494-1083 (ENGINEERING)
 OFFICE: 561-805-6716 (CONSTRUCTION SERVICES)
 SHEET C-4:
 MODIFIED "MANHOLE" S-5 IS SHOWN TO BE A CATCH BASIN,
 WHICH IS IT?
 SHEET C-5:
 1. ADDED NOTE TO DETAIL FOR WATER SERVICES "SEE DETAIL
 WS-1 ON SHEET C-7". ONLY 1 OR 2" SERVICES ARE ALLOWED.
 3/4" WATER SERVICES ARE NOT ALLOWED, DETAIL WS-1 WILL
 NEED TO BE FOLLOWED.
 2. THE METER SIZE FOR THE IRRIGATION SYSTEM WILL NEED
 TO BE CHANGED FROM A 3/4" WATER METER TO A 1". A 3/4"
 METER WILL ONLY SUPPLY 15 GALLONS PER MINUTE (GPM) AT A
 SAFE, CONTINUOUS OPERATING VOLUME. PER SHEET L-3
 (IRRIGATION PLANS), THE GPM USAGES ARE OVER THE SAFE,
 CONTINUOUS OPERATING VOLUME, WHICH IS ACTUALLY OVER THE
 ALLOWABLE FOR A 1" METER (25 GPM). EVEN WITH A 1" METER
 YOU WILL NOT BE ABLE TO MEET THE MINIMUM ALLOWABLE
 USAGE LEVELS OF A 1" METER, WITHOUT CHANGING THE
 IRRIGATION SYSTEM DESIGN, WHICH WILL NEED TO BE DONE TO
 REDUCE FOUR OF THE ZONES TO LESS THAN 25 GPM. THE
 ALTERNATIVE IS TO INCREASE THE METER SIZE (TO 1-1/2"]
 AND THE SERVICE SIZE [TO 2").
 3. PER OUR STANDARD DETAILS WATER METERS ARE NOT TO BE
 PLACED IN SIDEWALKS UNLESS THERE IS NO WHERE ELSE TO
 PLACE THEM. THESE TWO METERS NEED TO BE INSTALLED IN
 THE GRASS PARKWAY, SOUTH OF THE SIDEWALK.
 C-6:
 1. THE INTERIOR OPENING OF THE DUMPSTER ENCLOSURE IS
 SHOWN TO BE 12.5' WIDE, THIS IS SHOWN ON THE PLAN AND
 IS CORRECT. BUT, THE NOTE DESCRIBES THE GATES TO BE
 DESIGNED TO "FIT 10' OPENING & GATE POSTS." WE HAVE HAD
 PROBLEMS WITH ALLOWING THIS COMMENT IN THE PAST. IT IS
 NOT OUR RESPONSIBILITY TO PICK OUT EVER SMALL DETAIL,
 BUT BE WARNED, THE OPENING FOR THE GATES WILL NOT ONLY
 BE 12.5', THE PLACEMENT OF THE POSTS IS ON THE CENTER
 LINE OF THE 12" THICK BLOCKS, SO AN ADDITIONAL 10" WILL
 NEED TO BE ADDED TO THE WIDTH OF THE GATES. BE SURE YOU
 ORDER THE RIGHT MATERIAL.
 2. THE FIRST NOTE FOR THE EXFILTRATION TRENCH NEEDS TO
 BE CHANGED TO READ "SIDES, BOTTOM, AND TOP OF TRENCH TO
 BE LINED......."
 L-1:
 TREES ARE NOT ALLOWED TO BE PLANTED WITH LESS THAN 5'
 OF CLEARANCE BETWEEN THE OUTSIDE OF THE TREE ROOT BALL
 AND THE WATER OR SEWER LINE. THE PLAN SHOWS ONE TREE ON
 TOP OF THE SANITARY SEWER LATERAL, AND THREE MORE TREES
 THAT APPEAR TO BE TOO CLOSE. THERE ARE 4 TREES THAT
 APPEAR TOO CLOSE TO THE WATER SERVICE. REMOVE THE
 TREES, OR INSTALL PALMS AND USE A ROOT BARRIER BETWEEN
 THE UTILITY AND ROOT BALL.
  