2009-04-02 21:11:15 | ** PROVISO ** | | | | ** ALL PROVISO ITEMS SHALL BE REVISED ON PLANS, | | SUBMITTED, REVIEWED FOR CODE COMPLIANCE, PASSED AND ON | | JOBSITE BEFORE ANY ROUGH ELECTRICAL INSPECTION. FAILURE | | TO DO SO MAY CAUSE DELAY ON THE PROJECT SCHEDULE. A | | HOLD MAY BE PLACED ON ALL INSPECTIONS AND FEES MAY BE | | APPLIED. PLEASE BE SURE TO ADDRESS PROVISO ALONG WITH | | ANY REVISIONS BEFORE TIME STATED. | | | | 1) NOTE: ALL EMERGENCY AND EXIT LIGHTS SHALL BE | | CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT PER | | 700.12F. ** UNLESS AREAS MEETING EXCEPTION AND FIXTURE | | WIRING MEETS EXCEPTIONS. | | | | 2) NOTE: ENERGY CALCULATIONS DO NOT CONTAIN *GROSS | | ERRORS* AS STATED IN 13-103.3 HOWEVER THEY DO CONTAIN | | SOME MISSING FIXTURES WHICH ARE SHOWN ON PLANS. SEE F/ | | F1 FIXTURES ON EXTERIOR. PLEASE ALSO VERIFY J FIXTURE | | FOR THE LOCATION AS SHOWN. PLEASE KNOW THAT N FIXTURES | | DO SEEM TO MEET EXEMPTION.13-415.2.ABC.1.3 (B). MUST BE | | ON SEPARATE CONTROLS AS SHOWN. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|