Plan Review Notes
Plan Review Notes For Permit 09020147
Permit Number 09020147
Review Stop E
Sequence Number 2
Notes
Date Text
2009-04-02 21:11:15** PROVISO **
  
 ** ALL PROVISO ITEMS SHALL BE REVISED ON PLANS,
 SUBMITTED, REVIEWED FOR CODE COMPLIANCE, PASSED AND ON
 JOBSITE BEFORE ANY ROUGH ELECTRICAL INSPECTION. FAILURE
 TO DO SO MAY CAUSE DELAY ON THE PROJECT SCHEDULE. A
 HOLD MAY BE PLACED ON ALL INSPECTIONS AND FEES MAY BE
 APPLIED. PLEASE BE SURE TO ADDRESS PROVISO ALONG WITH
 ANY REVISIONS BEFORE TIME STATED.
  
 1) NOTE: ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT PER
 700.12F. ** UNLESS AREAS MEETING EXCEPTION AND FIXTURE
 WIRING MEETS EXCEPTIONS.
  
 2) NOTE: ENERGY CALCULATIONS DO NOT CONTAIN *GROSS
 ERRORS* AS STATED IN 13-103.3 HOWEVER THEY DO CONTAIN
 SOME MISSING FIXTURES WHICH ARE SHOWN ON PLANS. SEE F/
 F1 FIXTURES ON EXTERIOR. PLEASE ALSO VERIFY J FIXTURE
 FOR THE LOCATION AS SHOWN. PLEASE KNOW THAT N FIXTURES
 DO SEEM TO MEET EXEMPTION.13-415.2.ABC.1.3 (B). MUST BE
 ON SEPARATE CONTROLS AS SHOWN.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  