Plan Review Notes
Plan Review Notes For Permit 09020147
Permit Number 09020147
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-07 20:14:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-3 DETAIL 1. SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOT AREA
 FOR EACH ROOF DRAIN AND SHOW 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH DRAIN
 AREA IN ORDER TO VERIFY CALCULATIONS. (THE EAST SIDE OF
 THE ROOF AS SHOWN IS 11'3" MORE AREA AND MORE VERTICAL
 CONTRIBUTION, 11'3"X2), THEN THE WEST SIDE).
  
 2. SHT A-3 DETAIL 2 THE FLOW LINE OF THE OVERFLOW
 SCUPPER SHALL BE A MINIMUM OF 2 INCHES AND A MAXIMUM OF
 4 INCHES ABOVE THE ROOF PER SECTION 1503.4.3. PLEASE
 INDICATE ON DETAIL THE REQUIRED MEASUREMENT.
  
 3. SHT A11 ALL DETAILS 13 THRU 18. SHOW COMPLIANCE WITH
 THE FOLLOWING:
  
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
  
 ___LAVS"
 A. 11-4.19.2 HEIGHT
  
 ___SINK:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 4. SHT P3 DOMESTIC WATER RISER DIAGRAM. SHUT OFF VALVES
 ARE REQUIRED ON THE WATER SUPPLY PIPE TO EACH WALL
 HYDRANT. SECTION 606.2. -- THE RISER DIAGRAM SHOWS A
 TRAP PRIMER TO A FLOOR DRAIN FROM THE P6 FIXTURE THAT
 IS NOT SHOWN ON THE P1 FLOOR PLAN, NOR ON THE SANITARY
 DWV RISER DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1 &
 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  