2009-02-07 20:14:59 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A-3 DETAIL 1. SUBMIT CALCULATIONS FOR PRIMARY |
| AND SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH |
| ALL SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOT AREA |
| FOR EACH ROOF DRAIN AND SHOW 1/2 THE AREA OF ALL |
| VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH DRAIN |
| AREA IN ORDER TO VERIFY CALCULATIONS. (THE EAST SIDE OF |
| THE ROOF AS SHOWN IS 11'3" MORE AREA AND MORE VERTICAL |
| CONTRIBUTION, 11'3"X2), THEN THE WEST SIDE). |
| |
| 2. SHT A-3 DETAIL 2 THE FLOW LINE OF THE OVERFLOW |
| SCUPPER SHALL BE A MINIMUM OF 2 INCHES AND A MAXIMUM OF |
| 4 INCHES ABOVE THE ROOF PER SECTION 1503.4.3. PLEASE |
| INDICATE ON DETAIL THE REQUIRED MEASUREMENT. |
| |
| 3. SHT A11 ALL DETAILS 13 THRU 18. SHOW COMPLIANCE WITH |
| THE FOLLOWING: |
| |
| ___W/C'S: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT |
| |
| ___LAVS" |
| A. 11-4.19.2 HEIGHT |
| |
| ___SINK: |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| |
| 4. SHT P3 DOMESTIC WATER RISER DIAGRAM. SHUT OFF VALVES |
| ARE REQUIRED ON THE WATER SUPPLY PIPE TO EACH WALL |
| HYDRANT. SECTION 606.2. -- THE RISER DIAGRAM SHOWS A |
| TRAP PRIMER TO A FLOOR DRAIN FROM THE P6 FIXTURE THAT |
| IS NOT SHOWN ON THE P1 FLOOR PLAN, NOR ON THE SANITARY |
| DWV RISER DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1 & |
| 601.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |