2009-02-11 20:10:54 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THIS PLAN HAS BEEN REVIEWED FOR COMPLIANCE WITH THE |
| ABOVE REFERENCED CODES AND FOUND TO BE DEFICIENT IN THE |
| FOLLOWING: |
| |
| 1. PAGE M-1: EF-1 AND EF-2 HAVE EXHAUST DUCTS UNDER |
| POSITIVE PRESSURE WITHIN THE PLENUM CEILING AREA. |
| EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT BE |
| LOCATED WITHIN A PLENUM IN ACCORDANCE WITH FBCM 601.3. |
| |
| 2. NO OUTSIDE AIR CALCULATIONS COULD BE FOUND ON PLANS. |
| VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE |
| CAPACITY TO SUPPLY THE MINIMUM OUTDOOR AIRFLOW RATE |
| DETERMINED IN ACCORDANCE WITH FBCM TABLE 403.3 BASED ON |
| THE OCCUPANCY OF THE SPACE AND THE OCCUPANT LOAD OR |
| OTHER PARAMETER AS STATED THEREIN. PLEASE PROVIDE |
| OUTSIDE AIR CALCULATIONS SHOWING COMPLIANCE WITH FBCM |
| 403.3 OR 403.4. |
| |
| 3. NO COOLING LOAD CALCULATIONS COULD BE FOUND APPENDED |
| TO THE ENERGY CALCULATIONS. A COOLING LOAD CALCULATION |
| SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM SUBMITTED |
| TO THE BUILDING DEPARTMENT WHEN THE BUILDING IS |
| PERMITTED IN ACCORDANCE WITH FBCB 13-407.1.ABC.1. |
| SYSTEMS AND EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE |
| THAN THE SPACE AND SYSTEM LOADS CALCULATED IN |
| ACCORDANCE WITH THIS SECTION. |
| |
| 4. NOTE ON PAGE M-1 FLOOR PLAN CALLS FOR TWO TYPE E |
| DIFFUSERS TO HAVE COOLING AND HEATING SETPOINTS. PLEASE |
| CLARIFY THE DESIGN INTENT IN ACCORDANCE WIT FBCM 603.3 |
| AND FBCB 106.1.1. IT IS UNCLEAR HOW THESE DIFFUSERS, |
| WHICH ARE PART OF A CENTRALIZED SYSTEM WITHOUT |
| INDIVIDUAL CONTROLS ARE TO HAVE INDIVIDUAL SETPOINTS. |
| |
| 5. NO INFORMATION COULD BE FOUND IN PLANS OR SUBMITTALS |
| REGARDING WIND RESISTANCE CAPABILITIES OF THE RTUS AND |
| EXHAUST VENTS. MECHANICAL APPLIANCES AND EQUIPMENT |
| WHICH ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| INSTALLED TO RESIST WIND PRESSURES IN ACCORDANCE WITH |
| FBCM 301.13. PROVIDE MANUFACTURER???S DATA SHOWING RTUS |
| AND EXHAUST VENTS DESIGNED FOR WIND RESISTANCE. ALSO, |
| PROVIDE ATTACHMENT DETAILS WITH SUPPORTING WIND LOAD |
| CALCULATIONS FOR RTUS, VENT CAPS AND CURBS FOR BUILDING |
| PLAN REVIEW IN ACCORDANCE WITH THIS SECTION. |
| |
| 6. NO INFORMATION COULD BE FOUND ON PLANS REGARDING HOW |
| AUXILIARY DRAIN PROTECTION IS TO BE PROVIDED FOR RTUS. |
| AS AN ALTERNATIVE TO A SEPARATE DRAIN LINE, A |
| WATER-LEVEL DETECTION DEVICE THAT WILL SHUT OFF THE |
| EQUIPMENT SERVED PRIOR TO OVERFLOW OF THE PAN SHALL BE |
| PROVIDED IN ACCORDANCE WITH FBCM 307.2.3(2). THE |
| WATER-LEVEL DETECTION DEVICE SHALL CONNECT TO THE DRAIN |
| PAN AT A HIGHER LEVEL THAN THE PRIMARY DRAIN |
| CONNECTION. |
| |
| 7. NOTE #7 ON RTU SCHEDULE CALLS FOR DUCT SMOKE |
| DETECTORS TO BE INSTALLED ON THE RETURN AIR SYSTEM |
| WHILE THE RTU DETAIL SHOWS THE DUCT SMOKE DETECTOR ON |
| THE SUPPLY SIDE. PLEASE COORDINATE NOTES AND DETAILS |
| SHOWING COMPLIANCE WITH FBCM 606.2.1 (SUPPLY SIDE IS |
| CORRECT). PROVIDE AUDIBLE AND VISUAL NOTIFICATION IN |
| ACCORDANCE WITH FBCM 606.4. |
| |
| PLEASE RESPOND TO EACH COMMENT IN WRITING WITH AN |
| EXPLANATION OF HOW EACH COMMENT WAS ADDRESSED AS WELL |
| AS A DESCRIPTION OF WHERE THE RELATED INFORMATION CAN |
| BE FOUND. |
| |