Plan Review Notes For Permit 09020147 |
Permit Number |
09020147 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-02-12 14:22:04 | ***DENIED*** | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | SAFETY TO COMPLY WITH NFPA 101, 2006. THIS CURRENT | | EDITION HAS BEEN IN EFFECT SINCE DECEMBER 31, 2008. | | PLEASE ADD NOTE TO CODE SUMMARY. | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. THE CONSTRUCTION SITE SHALL BE CLEANED | | AND MAINTAINED DAILY OR MORE FREQUENTLY AS NECESSARY TO | | PROVIDE A SAFE OPERATION. | | | | 3) ADDRESS NUMBERS TO BE INSTALLED IN ACCORDANCE WITH | | THE REQUIREMENTS OF THE CITY OF WEST PALM BEACH FOR | | COMMERCIAL STRUCTURES, AND SHALL BE MINIMUM 6" IN | | HEIGHT, 1" WIDTH AND CONTRASTING WITH THE BACKGROUND. | | | | 4) PLEASE ADVISE WHAT MEANS WILL BE PROVIDED FOR | | EMERGENCY ACCESS INTO THE BUILDING AFTER NORMAL | | BUSINESS HOURS. (KNOX BOX OR OTHER APPROVED SECURED | | ENTRY SYSTEM) | | | | 5) DOORS SHALL COMPLY WITH SEC. 7.2.1, 101. | | | | 6) PLEASE PROVIDE FINISH CLASSIFICATION FOR FLOORS. | | | | 7) DUCT SMOKE DETECTORS TO BE INSTALLED IN SUPPLY DUCT | | IF ONLY PROVIDED WITH (1) APPLIANCE. SHEET M2 | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 | | | | |
|