2009-02-08 10:27:00 | ** DENIED REVIEW ** |
| |
| WACHOVIA BANK |
| |
| 1) NOTE: THERE ARE SEVERAL SHEETS OF PLANS MISSING |
| WHICH ARE LISTED ON THE COVER SHEET. THE CANOPY PLANS, |
| CIVIL, LANDSCAPE ETC. THERE ARE ITEMS ON SOME OF THESE |
| SHEETS WHICH MAY BE PART OF THE ELECTRICAL REVIEW. |
| PLEASE SUBMIT A COMPLETE SET OF PLANS FOR REVIEW. |
| FBC 106.3.5.1.2, 106.1.1, AS ADOPTED BY THE CITY OF |
| WEST PALM BEACH. |
| |
| |
| 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES ARE |
| LISTED ON THE ELECTRICAL PLAN SHEET E-1 AS WELL AS THE |
| COVER SHEET. THE COVER SHEET STATES THE 2004 FBC |
| HOWEVER THERE HAVE BEEN SEVERAL REVISIONS TO THIS |
| ORIGINAL ADOPTED CODE. PLEASE KNOW WE ARE CURRENTLY |
| UNDER THE 2007 REVISION TO THE 2004 FBC. THIS WOULD |
| INCLUDE 2005, 2006 REVISIONS AS WELL. THE 2006 |
| REVISIONS SUBSTANTIALLY REVISED MANY ITEMS UNDER |
| CHAPTER 13 ALONE. |
| ELECTRICAL ARE NOT SPECIFIC TO ANY PARTICULAR CODE. IT |
| STATES TO THE NATIONAL ELECTRICAL CODE HOWEVER NO |
| EDITION IS LISTED. |
| EVEN AS THE 2007 FBC HAS NOT BEEN ADOPTED AS OF |
| DECEMBER 31ST, 2008 THE LIFE SAFETY CODE NFPA-101 2006 |
| HAS BEEN ADOPTED. THIS CAN BE VERIFIED WITH THE STATE |
| FIRE MARSHAL OFFICE OR ON THEIR WEBSITE. |
| FS 553.73 |
| PLEASE SEE THE FOLLOWING ITEMS. |
| |
| 2004 FBC W/2007 REVISIONS. |
| 2006 NFPA-101 |
| 2005 NFPA-70 |
| |
| 3) NOTE: ** AS NOTED FOR INFORMATION ONLY. DEPENDING ON |
| WHEN PLANS ARE RESUBMITTED FOR REVIEW AND ISSUANCE. |
| MOST LICENSING REQUIRED FOR DESIGN PROFESSIONALS WILL |
| EXPIRE ON 2/28/09. PLEASE BE SURE TO UPDATE AS THIS |
| COULD DELAY ISSUANCE IF PERMIT/PLANS HAVE NOT BEEN |
| ISSUED BY THAT DATE. THIS IS NOTED FOR INFORMATION ONLY |
| AS THE LICENSING OF THE DESIGNER AND FIRM IS CURRENT AT |
| THIS TIME. |
| |
| 4) NOTE: PLEASE BE SURE COMPLIANCE WITH FBC CHAPTER 13 |
| IS MET. THERE ARE SEVERAL ITEMS WHICH WILL BE LISTED |
| BELOW. PLEASE ALSO BE AWARE OF COMMENTS FROM OTHER |
| TRADES AS THERE ARE OTHER COMPONENTS OF THE BUILDING |
| WHICH ARE MISSING FROM THE INPUT DATE REPORT OF THE |
| SUBMITTED ENERGY CALCULATIONS. SOME OF THESE WILL BE |
| NOTED BY THIS REVIEWER FOR INFORMATION AS SOME OF THESE |
| ITEMS AFFECT THE ELECTRICAL SYSTEMS OR HAVE DIRECT |
| CORRELATION. |
| SOME EXAMPLES WILL BE GIVEN AS A BENEFIT HOWEVER THEY |
| ARE IN NO WAY ALL POSSIBLE ITEMS WHICH DO NOT |
| COORDINATE WITH PLANS. THE INPUT DATA REPORT WILL BE |
| NOTED AS IDR BELOW. |
| |
| FOR EXAMPLE: PLEASE SEE FBC 13-411.1.ABC.2 FOR MINIMUM |
| PIPING INSULATION. THE PLANS DO CONTAIN ELECTRIC HOT |
| WATER SYSTEMS WHICH REQUIRED MINIMUM INSULATION. THE |
| IDR IS COMPLETELY BLANK FOR THIS ITEM. |
| |
| FOR EXAMPLE: THE IDR FOR LIST CARPET AND RUBBER PADDING |
| FOR ALL AREAS. THE MAIN ELECTRICAL ROOM AND OTHER AREAS |
| ARE NOT PERMITTED TO CONTAIN CARPET PER OTHER SECTIONS |
| OF THE FBC AS WELL AS THE NEC. IT IS PERMITTED TO |
| CREATE SPACES WITHIN ZONES. PLEASE SEE COMMENTS BELOW |
| WITH RESPECT TO THE NEC REQUIREMENTS OF THESE SPACES. |
| |
| FOR EXAMPLE: THE IDR FOR EXTERIOR LIGHTING IS NOT |
| COMPLETE. THE IDR ONLY CONTAINS 24-42WATT FIXTURES FOR |
| THE EXTERIOR. THIS IS NOT POSSIBLE WHEN THE PLANS |
| CLEARLY INDICATE MORE FIXTURES WITH HIGHER WATTAGES. |
| PLEASE ADJUST. |
| ONE TYPE OF FIXTURE ALONE IS THE *P1* FIXTURE WHICH IS |
| 400WATTS. THERE ARE NOT 400WA FIXTURES LISTED ON THE |
| IDR. |
| **THERE ARE ALSO SEVERAL OTHERS. |
| |
| FOR EXAMPLE: ALL LIGHTING ON THE IDR FOR INTERIOR IS |
| NOTED AS MANUAL ON/OFF. THIS DOES NOT COORDINATE WITH |
| PLANS. |
| |
| *** AS NOTED ABOVE THESE ARE SOME ITEMS GIVEN AS A |
| BENEFIT. PLEASE CALL TO GO OVER WITH ANY QUESTIONS OR |
| COMMENTS. |
| |
| 5) NOTE: AS NOTED ABOVE IT IS NOT PERMITTED TO HAVE ANY |
| CARPET OR COMBUSTIBLES IN THE ELECTRICAL ROOM OR SPACES |
| CONTAINING ELECTRICAL PANELS. |
| 240.24D,408.17 ETC |
| |
| 6) NOTE: PLEASE INCLUDE NOTES FOR REQUIRED SIGNAGE PER |
| 110.16. |
| |
| 7) NOTE: PLEASE SPECIFY TIME CLOCK AS NOTED FOR SOME |
| EXTERIOR LIGHTING SUCH AS SIGNS. ANY TIME CLOCKS FOR |
| EXTERIOR SHALL BE ASTRONOMICAL AND ARE REQUIRED TO |
| CONTAIN A MINIMUM OF 10HR BATTERY BACK UP. |
| MANY CONTAIN A LONGER BACK UP FOR PROGRAMMING THAN THE |
| MINIMUM 10HRS HOWEVER AS LONG AS THE MINIMUM IS MET |
| THIS WOULD BE OK. |
| |
| 8) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| FEEDERS AND BRANCH CIRCUITS. |
| PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED |
| THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES |
| A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END |
| DEVICE ON A CIRCUIT. THIS MAY GREATLY AFFECT FEEDERS OR |
| BRANCH CIRCUIT CONDUCTORS. |
| PLEASE SEE 13-413.1ABC.1. |
| |
| 9) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER |
| 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN |
| THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH FLORIDA |
| BUILDING COMMISSION/DCA. |
| |
| 10) NOTE: PLEASE INCLUDE EFFICIENCY RATINGS OF MOTORS |
| WHICH SHALL MEET 13-414.1.ABC.1.1. ( SEE NOTES FOR |
| ENERGY CALCULATIONS) |
| AS SOME PLANS WERE NOT SUBMITTED SOME ITEMS SUCH AS ANY |
| POSSIBLE MOTORS FOR IRRIGATION MAY OR MAY NOT BE NEEDED |
| TO BE INCLUDED. THIS WILL DEPEND ON HOW SYSTEM MAY BE |
| DESIGNED. |
| ** THIS IS NOTED FOR INFORMATION |
| |
| 11) NOTE: PLEASE PROVIDE MANUFACTURES SPECS/CUT SHEETS |
| FOR THE PROPOSED ROOF TOP UNITS WHICH STATES THE GFI |
| RECEPTACLES ARE FED FROM UNITS. |
| WHERE IS THE NEUTRAL BEING DERIVED? IF THIS EQUIPMENT |
| IS FED BY A 3-POLE BREAKER WITH NO NEUTRAL THEN THE GFI |
| MUST BE OBTAINING THE NEUTRAL AT SOME POINT. |
| IF THERE ARE TRANSFORMERS, THEN PLEASE INCLUDE THE |
| GROUNDING REQUIREMENTS FOR ANY SEPARATELY DERIVED |
| NEUTRAL. |
| 250.20 ETC |
| |
| 12) NOTE: PLEASE KNOW THE LOCATION OF THE SERVICE MEANS |
| OF DISCONNECT IS LOCATED TOO FAR INSIDE THE BUILDING. |
| IN THE EVENT OF AN EMERGENCY THE FIRE DEPARTMENT |
| PERSONNEL OR OTHERS MAY NEED TO SHUT DOWN THE |
| ELECTRICAL SYSTEM. BASED ON THE PLANS THERE ARE NO |
| DOORS DIRECTLY FROM OUTSIDE TO THIS ROOM. IN FACT THE |
| PLANS SHOW MULTIPLE DOORS IN ORDER TO ACCESS ELECTRICAL |
| EQUIPMENT. THIS BUILDING IS NOT SPRINKLED WHICH IS A |
| HIGHER HAZARD. |
| PLEASE ALSO KNOW THAT BASED ON RISER AS SHOWN THERE ARE |
| ALSO UNPROTECTED CONDUCTORS INSIDE THE BUILDING WHICH |
| IS NOT PERMITTED BASED ON THE AMOUNT AS SHOWN. |
| PLEASE ADJUST. |
| 230.70 |
| THESE ARE ALSO NOT READILY ACCESSIBLE BASED ON THE |
| PLANS SUBMITTED. |
| |
| 13) NOTE: PLEASE CLARIFY THE SYMBOL ON THE PLANS SHOWN |
| ON THE PLANS IN THE MAIN ELECTRICAL ROOM. THIS SEEMS TO |
| BE A TYPICAL SYMBOL FOR A TRANSFORMER HOWEVER BASED ON |
| THE ELECTRICAL SYSTEM BEING PROVIDED THERE IS NO NEED |
| FOR ANY SUCH DEVICE. |
| IF THIS WAS A TRANSFORMER BASED ON LOCATION IT WOULD |
| NOT MEET 110.26. WHAT IS THIS ? |
| |
| 14) NOTE: PLEASE SEE 250.6,250.524. THE RISER INDICATES |
| AN EQUIPMENT GROUNDING CONDUCTOR FROM FPL TO THE FIRST |
| MEANS OF DISCONNECT WHICH IS NOT PERMITTED. PLEASE BE |
| SURE TO KEEP IN MIND COMMENT #12 ABOVE WITH RESPECT TO |
| MAIN(S). |
| |
| 15) NOTE: BASED ON THE PLANS AND THE SIZE OF THE |
| SATELLITE UNDER FEDERAL CODE OF REGULATION THE UNIT |
| ITSELF IS NOT REQUIRED TO BE PERMITTED HOWEVER ANY |
| PENETRATIONS DO FALL UNDER THE BUILDING CODE AS WELL AS |
| THE NEC. ( NO FIRE RATINGS HOWEVER SEE POSSIBLE |
| COMMENTS FROM BUILDING REVIEW) |
| ** THIS IS NOTED FOR INFORMATION. |
| |
| 16) NOTE: THE PLANS ARE MISSING THE CANOPY PLANS WHICH |
| WAS NOTED ABOVE HOWEVER BASED ON THE ELECTRICAL PLANS |
| THERE WILL BE SEVERAL ELECTRICAL ITEMS IN THIS |
| STRUCTURE. WILL THIS BE CONSIDERED A SEPARATE BUILDING |
| BY DEFINITION OF THE FBC? IF SO THIS WILL AFFECT |
| SEVERAL ASPECTS OF THE PLANS INCLUDING INSPECTIONS. |
| PLEASE KNOW THAT ANY STRUCTURAL STEEL AS WELL AS |
| FOUNDATION STEEL SHALL BE BONDED/PART OF THE ELECTRICAL |
| SYSTEM FROM THE MAIN BANK BUILDING AS THESE SYSTEM MOST |
| CERTAINLY CROSS. |
| 250.50, 250.90-250.104. |
| THERE IS A NEED TO CLEAR UP WHEN THIS STRUCTURE IS |
| GOING TO BE DONE. PLEASE SEE NOTES FROM OTHER TRADES AS |
| THIS WILL AFFECT PERMITTING WITH MULTIPLE CONTRACTORS |
| FOR THE SAME BUILDING/SITE. LETTERS OF UNDERSTANDING |
| BETWEEN SEPARATE CONTRACTORS WILL BE REQUIRED AS PLANS |
| NOTES MENTIONS THIS WILL BE DONE BY A SEPARATE |
| CONTRACTOR. |
| |
| FBC 106.1.1,106.1.2, 106.3.5.1.2, 106.5. FOR CLARITY, |
| COORDINATION, MINIMUM AND RECORD PLANS. |
| |
| 17) NOTE: PLEASE SEE 220,230.42,215.3 ETC OF THE NEC. |
| PLEASE SHOW ALL LOADS FOR BUILDING INCLUDING THAT OF |
| ALL CONTINUOUS LOADS. |
| PLEASE SEE 422.13 AS THE WATER HEATER APPEARS TO BE A |
| STORAGE TYPE UNIT. THIS REQUIRES THE LOAD TO BE SHOWN |
| AS A CONTINUOUS LOAD UNDER THE 2005 NEC. |
| PLEASE REVISE CALCULATIONS. |
| |
| 18) NOTE: PLEASE COORDINATE PLANS FOR ALL CIRCUITING |
| WITH THE SUBMITTED PANEL SCHEDULES. AN EXAMPLE IS THE |
| SITE LIGHTING PLANS WHICH INDICATES THE WACHOVIA SIGN |
| AS CIRCUIT A-36, HOWEVER BASED ON THE PANEL SCHEDULE |
| THIS IS A CIRCUIT FOR THE BLOWER VAT. |
| ** THIS IS ONE NOTED AS A BENEFIT. |
| 408.4. |
| FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| |
| 19) NOTE: PLEASE CLARIFY THE TYPE OF DEVICES SHOWN FOR |
| MANY ROOMS FOR LIGHTING CONTROLS. THE SYMBOL LEGEND |
| STATES *MOTION SENSORS*. ARE THESE MOTION SENSORS OR |
| OCCUPANCY SENSORS? |
| PLEASE SEE 13-415.1.ABC.1.2 AS SPACE CONTROLS FOR ROOMS |
| SUCH AS CONFERENCE AND BREAK ROOMS. PLEASE SPECIFY |
| TIMES. |
| |
| 20) NOTE: PLEASE PLACES NOTES ON PLANS FOR 410.73G |
| |
| 21) NOTE: THE PLANS INDICATE A TELE/DATA ROOM. THERE IS |
| NO INDICATION THAT THIS ROOM IS AN IT ROOM AND PLANS DO |
| NOT SHOW ANY ITEMS PER 645.4. AS THIS DOES NOT FALL |
| UNDER THE DEFINITIONS PER THE SECTION GIVEN PLEASE |
| PLACE NOTES ON PLANS WHICH STATES * NO WIRING METHODS |
| PER NEC 645 IS PERMITTED* OR WORDS TO THAT AFFECT. |
| IT MAY BE A BENEFIT TO CONTACT ANY IT PERSONNEL FOR |
| BANK TO FIND OUT THE WIRING METHODS TO BE USED. |
| |
| 22) NOTE: PLANS STATES TO MOUNT A RECEPTACLE ABOVE |
| CEILING FOR THE * DYE PACK UNIT*. AS THIS UNIT IS NOT |
| HARD WIRED BASED ON THE RECEPTACLE REQUIREMENTS IT IS |
| IMPORTANT TO SEE NEC 400.8(5). CORDS ARE NOT PERMITTED |
| ABOVE SUSPENDED CEILINGS. |
| PLEASE REVISE. |
| |
| 23) NOTE: PLEASE SEE 110.26D |
| |
| ** AS THERE ARE SOME ITEMS BEING REVISED WHICH WILL |
| AFFECT PLANS SUBSTANTIALLY THERE MAY BE NEW COMMENTS ON |
| THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| TIME. |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |