2009-02-08 10:27:00** DENIED REVIEW **
  
 WACHOVIA BANK
  
 1) NOTE: THERE ARE SEVERAL SHEETS OF PLANS MISSING
 WHICH ARE LISTED ON THE COVER SHEET. THE CANOPY PLANS,
 CIVIL, LANDSCAPE ETC. THERE ARE ITEMS ON SOME OF THESE
 SHEETS WHICH MAY BE PART OF THE ELECTRICAL REVIEW.
 PLEASE SUBMIT A COMPLETE SET OF PLANS FOR REVIEW.
 FBC 106.3.5.1.2, 106.1.1, AS ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES ARE
 LISTED ON THE ELECTRICAL PLAN SHEET E-1 AS WELL AS THE
 COVER SHEET. THE COVER SHEET STATES THE 2004 FBC
 HOWEVER THERE HAVE BEEN SEVERAL REVISIONS TO THIS
 ORIGINAL ADOPTED CODE. PLEASE KNOW WE ARE CURRENTLY
 UNDER THE 2007 REVISION TO THE 2004 FBC. THIS WOULD
 INCLUDE 2005, 2006 REVISIONS AS WELL. THE 2006
 REVISIONS SUBSTANTIALLY REVISED MANY ITEMS UNDER
 CHAPTER 13 ALONE.
 ELECTRICAL ARE NOT SPECIFIC TO ANY PARTICULAR CODE. IT
 STATES TO THE NATIONAL ELECTRICAL CODE HOWEVER NO
 EDITION IS LISTED.
 EVEN AS THE 2007 FBC HAS NOT BEEN ADOPTED AS OF
 DECEMBER 31ST, 2008 THE LIFE SAFETY CODE NFPA-101 2006
 HAS BEEN ADOPTED. THIS CAN BE VERIFIED WITH THE STATE
 FIRE MARSHAL OFFICE OR ON THEIR WEBSITE.
 FS 553.73
 PLEASE SEE THE FOLLOWING ITEMS.
  
 2004 FBC W/2007 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
  
 3) NOTE: ** AS NOTED FOR INFORMATION ONLY. DEPENDING ON
 WHEN PLANS ARE RESUBMITTED FOR REVIEW AND ISSUANCE.
 MOST LICENSING REQUIRED FOR DESIGN PROFESSIONALS WILL
 EXPIRE ON 2/28/09. PLEASE BE SURE TO UPDATE AS THIS
 COULD DELAY ISSUANCE IF PERMIT/PLANS HAVE NOT BEEN
 ISSUED BY THAT DATE. THIS IS NOTED FOR INFORMATION ONLY
 AS THE LICENSING OF THE DESIGNER AND FIRM IS CURRENT AT
 THIS TIME.
  
 4) NOTE: PLEASE BE SURE COMPLIANCE WITH FBC CHAPTER 13
 IS MET. THERE ARE SEVERAL ITEMS WHICH WILL BE LISTED
 BELOW. PLEASE ALSO BE AWARE OF COMMENTS FROM OTHER
 TRADES AS THERE ARE OTHER COMPONENTS OF THE BUILDING
 WHICH ARE MISSING FROM THE INPUT DATE REPORT OF THE
 SUBMITTED ENERGY CALCULATIONS. SOME OF THESE WILL BE
 NOTED BY THIS REVIEWER FOR INFORMATION AS SOME OF THESE
 ITEMS AFFECT THE ELECTRICAL SYSTEMS OR HAVE DIRECT
 CORRELATION.
 SOME EXAMPLES WILL BE GIVEN AS A BENEFIT HOWEVER THEY
 ARE IN NO WAY ALL POSSIBLE ITEMS WHICH DO NOT
 COORDINATE WITH PLANS. THE INPUT DATA REPORT WILL BE
 NOTED AS IDR BELOW.
  
 FOR EXAMPLE: PLEASE SEE FBC 13-411.1.ABC.2 FOR MINIMUM
 PIPING INSULATION. THE PLANS DO CONTAIN ELECTRIC HOT
 WATER SYSTEMS WHICH REQUIRED MINIMUM INSULATION. THE
 IDR IS COMPLETELY BLANK FOR THIS ITEM.
  
 FOR EXAMPLE: THE IDR FOR LIST CARPET AND RUBBER PADDING
 FOR ALL AREAS. THE MAIN ELECTRICAL ROOM AND OTHER AREAS
 ARE NOT PERMITTED TO CONTAIN CARPET PER OTHER SECTIONS
 OF THE FBC AS WELL AS THE NEC. IT IS PERMITTED TO
 CREATE SPACES WITHIN ZONES. PLEASE SEE COMMENTS BELOW
 WITH RESPECT TO THE NEC REQUIREMENTS OF THESE SPACES.
  
 FOR EXAMPLE: THE IDR FOR EXTERIOR LIGHTING IS NOT
 COMPLETE. THE IDR ONLY CONTAINS 24-42WATT FIXTURES FOR
 THE EXTERIOR. THIS IS NOT POSSIBLE WHEN THE PLANS
 CLEARLY INDICATE MORE FIXTURES WITH HIGHER WATTAGES.
 PLEASE ADJUST.
 ONE TYPE OF FIXTURE ALONE IS THE *P1* FIXTURE WHICH IS
 400WATTS. THERE ARE NOT 400WA FIXTURES LISTED ON THE
 IDR.
 **THERE ARE ALSO SEVERAL OTHERS.
  
 FOR EXAMPLE: ALL LIGHTING ON THE IDR FOR INTERIOR IS
 NOTED AS MANUAL ON/OFF. THIS DOES NOT COORDINATE WITH
 PLANS.
  
 *** AS NOTED ABOVE THESE ARE SOME ITEMS GIVEN AS A
 BENEFIT. PLEASE CALL TO GO OVER WITH ANY QUESTIONS OR
 COMMENTS.
  
 5) NOTE: AS NOTED ABOVE IT IS NOT PERMITTED TO HAVE ANY
 CARPET OR COMBUSTIBLES IN THE ELECTRICAL ROOM OR SPACES
 CONTAINING ELECTRICAL PANELS.
 240.24D,408.17 ETC
  
 6) NOTE: PLEASE INCLUDE NOTES FOR REQUIRED SIGNAGE PER
 110.16.
  
 7) NOTE: PLEASE SPECIFY TIME CLOCK AS NOTED FOR SOME
 EXTERIOR LIGHTING SUCH AS SIGNS. ANY TIME CLOCKS FOR
 EXTERIOR SHALL BE ASTRONOMICAL AND ARE REQUIRED TO
 CONTAIN A MINIMUM OF 10HR BATTERY BACK UP.
 MANY CONTAIN A LONGER BACK UP FOR PROGRAMMING THAN THE
 MINIMUM 10HRS HOWEVER AS LONG AS THE MINIMUM IS MET
 THIS WOULD BE OK.
  
 8) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED
 THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES
 A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END
 DEVICE ON A CIRCUIT. THIS MAY GREATLY AFFECT FEEDERS OR
 BRANCH CIRCUIT CONDUCTORS.
 PLEASE SEE 13-413.1ABC.1.
  
 9) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN
 THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH FLORIDA
 BUILDING COMMISSION/DCA.
  
 10) NOTE: PLEASE INCLUDE EFFICIENCY RATINGS OF MOTORS
 WHICH SHALL MEET 13-414.1.ABC.1.1. ( SEE NOTES FOR
 ENERGY CALCULATIONS)
 AS SOME PLANS WERE NOT SUBMITTED SOME ITEMS SUCH AS ANY
 POSSIBLE MOTORS FOR IRRIGATION MAY OR MAY NOT BE NEEDED
 TO BE INCLUDED. THIS WILL DEPEND ON HOW SYSTEM MAY BE
 DESIGNED.
 ** THIS IS NOTED FOR INFORMATION
  
 11) NOTE: PLEASE PROVIDE MANUFACTURES SPECS/CUT SHEETS
 FOR THE PROPOSED ROOF TOP UNITS WHICH STATES THE GFI
 RECEPTACLES ARE FED FROM UNITS.
 WHERE IS THE NEUTRAL BEING DERIVED? IF THIS EQUIPMENT
 IS FED BY A 3-POLE BREAKER WITH NO NEUTRAL THEN THE GFI
 MUST BE OBTAINING THE NEUTRAL AT SOME POINT.
 IF THERE ARE TRANSFORMERS, THEN PLEASE INCLUDE THE
 GROUNDING REQUIREMENTS FOR ANY SEPARATELY DERIVED
 NEUTRAL.
 250.20 ETC
  
 12) NOTE: PLEASE KNOW THE LOCATION OF THE SERVICE MEANS
 OF DISCONNECT IS LOCATED TOO FAR INSIDE THE BUILDING.
 IN THE EVENT OF AN EMERGENCY THE FIRE DEPARTMENT
 PERSONNEL OR OTHERS MAY NEED TO SHUT DOWN THE
 ELECTRICAL SYSTEM. BASED ON THE PLANS THERE ARE NO
 DOORS DIRECTLY FROM OUTSIDE TO THIS ROOM. IN FACT THE
 PLANS SHOW MULTIPLE DOORS IN ORDER TO ACCESS ELECTRICAL
 EQUIPMENT. THIS BUILDING IS NOT SPRINKLED WHICH IS A
 HIGHER HAZARD.
 PLEASE ALSO KNOW THAT BASED ON RISER AS SHOWN THERE ARE
 ALSO UNPROTECTED CONDUCTORS INSIDE THE BUILDING WHICH
 IS NOT PERMITTED BASED ON THE AMOUNT AS SHOWN.
 PLEASE ADJUST.
 230.70
 THESE ARE ALSO NOT READILY ACCESSIBLE BASED ON THE
 PLANS SUBMITTED.
  
 13) NOTE: PLEASE CLARIFY THE SYMBOL ON THE PLANS SHOWN
 ON THE PLANS IN THE MAIN ELECTRICAL ROOM. THIS SEEMS TO
 BE A TYPICAL SYMBOL FOR A TRANSFORMER HOWEVER BASED ON
 THE ELECTRICAL SYSTEM BEING PROVIDED THERE IS NO NEED
 FOR ANY SUCH DEVICE.
 IF THIS WAS A TRANSFORMER BASED ON LOCATION IT WOULD
 NOT MEET 110.26. WHAT IS THIS ?
  
 14) NOTE: PLEASE SEE 250.6,250.524. THE RISER INDICATES
 AN EQUIPMENT GROUNDING CONDUCTOR FROM FPL TO THE FIRST
 MEANS OF DISCONNECT WHICH IS NOT PERMITTED. PLEASE BE
 SURE TO KEEP IN MIND COMMENT #12 ABOVE WITH RESPECT TO
 MAIN(S).
  
 15) NOTE: BASED ON THE PLANS AND THE SIZE OF THE
 SATELLITE UNDER FEDERAL CODE OF REGULATION THE UNIT
 ITSELF IS NOT REQUIRED TO BE PERMITTED HOWEVER ANY
 PENETRATIONS DO FALL UNDER THE BUILDING CODE AS WELL AS
 THE NEC. ( NO FIRE RATINGS HOWEVER SEE POSSIBLE
 COMMENTS FROM BUILDING REVIEW)
 ** THIS IS NOTED FOR INFORMATION.
  
 16) NOTE: THE PLANS ARE MISSING THE CANOPY PLANS WHICH
 WAS NOTED ABOVE HOWEVER BASED ON THE ELECTRICAL PLANS
 THERE WILL BE SEVERAL ELECTRICAL ITEMS IN THIS
 STRUCTURE. WILL THIS BE CONSIDERED A SEPARATE BUILDING
 BY DEFINITION OF THE FBC? IF SO THIS WILL AFFECT
 SEVERAL ASPECTS OF THE PLANS INCLUDING INSPECTIONS.
 PLEASE KNOW THAT ANY STRUCTURAL STEEL AS WELL AS
 FOUNDATION STEEL SHALL BE BONDED/PART OF THE ELECTRICAL
 SYSTEM FROM THE MAIN BANK BUILDING AS THESE SYSTEM MOST
 CERTAINLY CROSS.
 250.50, 250.90-250.104.
 THERE IS A NEED TO CLEAR UP WHEN THIS STRUCTURE IS
 GOING TO BE DONE. PLEASE SEE NOTES FROM OTHER TRADES AS
 THIS WILL AFFECT PERMITTING WITH MULTIPLE CONTRACTORS
 FOR THE SAME BUILDING/SITE. LETTERS OF UNDERSTANDING
 BETWEEN SEPARATE CONTRACTORS WILL BE REQUIRED AS PLANS
 NOTES MENTIONS THIS WILL BE DONE BY A SEPARATE
 CONTRACTOR.
  
 FBC 106.1.1,106.1.2, 106.3.5.1.2, 106.5. FOR CLARITY,
 COORDINATION, MINIMUM AND RECORD PLANS.
  
 17) NOTE: PLEASE SEE 220,230.42,215.3 ETC OF THE NEC.
 PLEASE SHOW ALL LOADS FOR BUILDING INCLUDING THAT OF
 ALL CONTINUOUS LOADS.
 PLEASE SEE 422.13 AS THE WATER HEATER APPEARS TO BE A
 STORAGE TYPE UNIT. THIS REQUIRES THE LOAD TO BE SHOWN
 AS A CONTINUOUS LOAD UNDER THE 2005 NEC.
 PLEASE REVISE CALCULATIONS.
  
 18) NOTE: PLEASE COORDINATE PLANS FOR ALL CIRCUITING
 WITH THE SUBMITTED PANEL SCHEDULES. AN EXAMPLE IS THE
 SITE LIGHTING PLANS WHICH INDICATES THE WACHOVIA SIGN
 AS CIRCUIT A-36, HOWEVER BASED ON THE PANEL SCHEDULE
 THIS IS A CIRCUIT FOR THE BLOWER VAT.
 ** THIS IS ONE NOTED AS A BENEFIT.
 408.4.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 19) NOTE: PLEASE CLARIFY THE TYPE OF DEVICES SHOWN FOR
 MANY ROOMS FOR LIGHTING CONTROLS. THE SYMBOL LEGEND
 STATES *MOTION SENSORS*. ARE THESE MOTION SENSORS OR
 OCCUPANCY SENSORS?
 PLEASE SEE 13-415.1.ABC.1.2 AS SPACE CONTROLS FOR ROOMS
 SUCH AS CONFERENCE AND BREAK ROOMS. PLEASE SPECIFY
 TIMES.
  
 20) NOTE: PLEASE PLACES NOTES ON PLANS FOR 410.73G
  
 21) NOTE: THE PLANS INDICATE A TELE/DATA ROOM. THERE IS
 NO INDICATION THAT THIS ROOM IS AN IT ROOM AND PLANS DO
 NOT SHOW ANY ITEMS PER 645.4. AS THIS DOES NOT FALL
 UNDER THE DEFINITIONS PER THE SECTION GIVEN PLEASE
 PLACE NOTES ON PLANS WHICH STATES * NO WIRING METHODS
 PER NEC 645 IS PERMITTED* OR WORDS TO THAT AFFECT.
 IT MAY BE A BENEFIT TO CONTACT ANY IT PERSONNEL FOR
 BANK TO FIND OUT THE WIRING METHODS TO BE USED.
  
 22) NOTE: PLANS STATES TO MOUNT A RECEPTACLE ABOVE
 CEILING FOR THE * DYE PACK UNIT*. AS THIS UNIT IS NOT
 HARD WIRED BASED ON THE RECEPTACLE REQUIREMENTS IT IS
 IMPORTANT TO SEE NEC 400.8(5). CORDS ARE NOT PERMITTED
 ABOVE SUSPENDED CEILINGS.
 PLEASE REVISE.
  
 23) NOTE: PLEASE SEE 110.26D
  
 ** AS THERE ARE SOME ITEMS BEING REVISED WHICH WILL
 AFFECT PLANS SUBSTANTIALLY THERE MAY BE NEW COMMENTS ON
 THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  