 BUILDING PLAN REVIEW
 PERMIT: 09020147
 ADD: 1615 PALM BEACH LAKES BLVD
 CONT: RCC ASSOCIATES, INC
 TEL: (954)691-5385
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1CINFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THE COVERSHEET
 FAILS TO INCLUDE THE 2005,2006 AND 2007 SUPPLEMENTS.
  
 2) THE COVERSHEET INDICATES CIVIL AND LANDSCAPE PLANS
 ARE INCLUDED WITHIN THE SET OF PLANS, BUT NO SUCH PLANS
 ARE INCLUDED WITHIN THESE SETS OF PLANS. PLANS CAN NOT
 BE CHECKED FOR COMPLIANCE (106.3.5.1.1(1) SITE PARKING)
 FOR THE FOLLOWING ITEMS:
  
 2A) 1-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES:
 NEW CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1, 1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3(5) OF THIS
 CODE.
 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM
 REQUIREMENTS:
 (1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
 (5) PARKING SPACES:
 (A) IF PARKING SPACES ARE PROVIDED FOR SELF-PARKING BY
 EMPLOYEES OR VISITORS, OR BOTH, THEN ACCESSIBLE SPACES
 COMPLYING WITH SECTION 11-4.6 SHALL BE PROVIDED IN EACH
 SUCH PARKING AREA. SUCH SPACES SHALL BE DESIGNED AND
 MARKED FOR EXCLUSIVE USE OF THOSE INDIVIDUALS WHO HAVE
 A SEVERE PHYSICAL DISABILITY AND HAVE PERMANENT OR
 TEMPORARY MOBILITY PROBLEMS THAT SUBSTANTIALLY IMPAIR
 THEIR ABILITY TO AMBULATE AND WHO HAVE BEEN ISSUED
 EITHER A DISABLED PARKING PERMIT UNDER SECTION 316.1958
 OR 320.0848, FLORIDA STATUTES, OR A LICENSE PLATE UNDER
 SECTION 320.084, 320.0842, 320.0843, OR 320.0845,
 FLORIDA STATUTES. THE NUMBER OF ACCESSIBLE PARKING
 SPACES SHALL COMPLY WITH THE TABLE BELOW
 C) IF PASSENGER LOADING ZONES ARE PROVIDED, THEN AT
 LEAST ONE PASSENGER LOADING ZONE SHALL COMPLY WITH
 SECTION 11-4.6.6.
  
  
 3) THE COVER SHEET INDICATES THERE TO BE CANOPY PLANS
 WITHIN THE SET OF PLANS, THE CANOPY
 IS ILLUSTRATED ON THE FLOOR PLAN, ELEVATIONS BUT THE
 STRUCTURAL SHEET S-1 HAS A NOTE ??? FOUNDATION AND
 CANOPY FRAMING BY OTHERS. THE DESCRIPTION OF THE
 PROJECT ON THE PERMIT APPLICATION DOES NOT INDICATE IF
 THE CANOPY IS TO BE PART OF THIS PERMIT. 106.1.2
 ADDITIONAL INFORMATION REQUIRED. IF THE CANOPY IS TO BE
 PART OF THIS PERMIT THEN PLANS WILL BE REQUIRED
 106.3.5.1.1(8) STRUCTURAL REQUIREMENTS.
  
 SHEET A5 DETAIL# 4 INDICATES THE CANOPY IS TO BE
 SUPPLIED AND INSTALLED BY THE MCGEE CORPORATION,
 MATTHEW, N. C. 1-800-526-5589. IF THIS STRUCTURE IS TO
 BE BUILT UNDER A SEPARATE PERMIT THEN A LETTER FROM
 BOTH THE CGC AND CBC THAT THEY HAVE NO PROBLEMS WITH
 THE OTHER WHILE WORKING WITHIN THE SAME SITE, LETTER TO
 BE NOTARIZED BY THE QUALIFIER ON THEIR LETTERHEAD.
  
 4) SOILS REPORTS, NO SOILS REPORTS WERE SUBMITTED
 PROVIDING THE MINIMUM SAFE BEARING VALUE OF THE SOILS.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
 SOILS REPORTS SHOULD MAKE REFERENCE TO THE TWO
 INDEPENDENT STRUCTURES AND TYPE OF FOOTINGS, BUILDING
 AND DRIVE THRU STRUCTURE.
  
 5A) NOTE, THESE PLANS WERE PREPARED UNDER THE 2004 FBC
 BASE CODE, SO THE PRODUCT APPROVALS TO BE SUBMITTED ARE
 TO READ CODE VERSION 2004 NOT 2007 AS LISTED BELOW???
 (1) FL2887-R2/2007 VISTA WALL- PANEL WALL- STOREFRONT
 (3 SETS)
 (2) FL1601-R5/2007 CARLISLE SYNTEC INCORPORATED (3
 SETS)
  
 5B) NOTE, SINCE 3 SETS OF PLANS AND SOME PRODUCT
 APPROVALS THESE ARE THE APPROVALS WHERE LESS WERE
 SUBMITTED:
 (1) GLAZED EXTERIOR DOORS, VISTAWALL INDICATES DOORS
 ARE COVERED UNDER A SEPARATE
 SUBMISSION
 (2) ROOF HATCHES- 1609.6.2.2 COMPONENTS AND CLADDING AS
 WELL AS FLORIDA LAW
 RULE 9B-72.32(31) (A) PRE-ENGINEERED ROOF ACCESS
 HATCHES
 (3) WINDOW TYPE ???D??? PROVIDED BY BANK EQUIPMENT
 SUPPLIER.
  
 5C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5D) WHILE NOT A TRUE PRODUCT APPROVAL IT TIES IN TO
 COMPONENTS AND CLADDING, THE RTU UNITS THAT TIE DOWN TO
 THE ROOF, PLEASE PROVIDE TWO ITEMS:
 (1) THE ACTUAL RESTRAINT FOR THE CURB TO ROOF AND THE
 UNIT TO THE CURB, COMPONENTS AND
 CLADDING 1609.6.2.2. SHOW COMPLIANCE WITH THE TTIE DOWN
 OF THE CURB TO ROOF SYSTEM AND UNIT TO CURB.
 (2) DEALS WITH THE ROOF TOP EQUIPMENT: 301.13 FBC
 MECHANICAL CODE
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED
 (THE UNITS THEMSELVES) AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 6) ROOFING:
 6A) ROOFING PRODUCT APPROVAL CARLISLE SYNTEC
 INCORPORATED CORRECT VERSION IS FL1601-R4
 (2004 FBC) THE INFORMATION SUBMITTED IS A GUIDE-SPEC
 FOR SURE WELD FULLY ADHERED ROOFING SYSTEM. THERE IS NO
 INSTALLATION INFORMATION PROVIDED NOR THE PSF THIS
 SYSTEM WILL BE ABLE TO WITHSTAND NOR LIMITATIONS FOR
 FASTENER LENGTHS. 1609.6.2.2.
  
  
 6B) ROOF INSULATION SHEET A5 & A6 BOTH INDICATE THE USE
 OF A FIBER FACED POLYISOCYANURATE
 ROOF INSULATION WITH A R-VALUE OF 21. PLEASE NOTE THAT
 THE MINIMUM R-21 VALUE WILL NEED TO BE AT THE ROOF
 DRAINS AND SLOPE UP FROM THERE. PLEASE PROVIDE SHOP
 DRAWINGS INDICATING THE DEPTH OF THE INSULATION AT THE
 OPPOSITE WALL OF THE ROOF DRAINS. FL 61G1-23.015 (2)
 THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC...
  
 PROVIDE ALSO THE CALCULATIONS FOR FASTENERS. LENGTH OF
 FASTENERS IS A CONCERN USING A JOHNS MANSVILLE FESCO
 FOAM ALSO A POLYISOCYNURATE AND LAMINATOR BOARD THE
 DEPTH OF THE FOAM APPEARS TO BE APPROXIMATELY 3.7
 INCHES AT THE ROOF DRAIN FOR A R-21 AND 14 INCHES AT
 THE OPPOSITE WALL 42 FEET AWAY. PLEASE SEE ENCLOSED FL
 INFORMAL CODE INTERPRETATIONS.
  
 6C) THE A5 & A-6 SHEET INDICATE A R-VALUE OF 21 USING A
 POLYISOCYNURATE FOAM WHILE THE ENERGY CALCULATION
 INDICATES THE USE OF A AGRIBOARD ROOF INSULATION AGAIN
 PLEASE CORRELATE YOUR DATA AND SUBMIT OR RESUBMIT. NOTE
 THE AGRIBOARD PANEL INSULATING VALUE OF 25.44 IS A
 PANEL 7-7/8??? THAT WOULD STILL NEED ????? PER FOOT OF
 (2%)SLOPE FOR THE ROOFING SYSTEMS DRAINAGE
 REQUIREMENTS. SECTION 1507.13.1.
  
 7) DISCREPANCIES BETWEEN THE ENERGY INPUT DATA REPORT
 AND THE ARCHITECTURAL PLANS. THE INPUT DATA REPORT
 UNDER WALLS INDICATES 25.6 R-VALUE FOR A
 STUCCO/AGRIBOARD/ GYPSUM BOARD WALL SYSTEM WHERE AS
 SHEET A5 & A6 BOTH INDICATE THE USE OF STUCCO, CMU,
 1 /12 INCH THICK POLYSTYRENE (R-11) AND 5/8??? GYP
 BOARD. PLEASE CORRECT, AND CORRELATE DOCUMENTS. 106.1.2
 ADDITIONAL INFORMATION REQUIRED. 13-400.0.A.
  
 8) INPUT DATA REPORT EXTERIOR DOORS IS LEFT BLANK
 PLEASE REVIEW SHEET A1 DOOR 120B IS A INSULATED
 EXTERIOR METAL DOOR.
  
 9) THE INPUT DATA REPORT HAS TAKEN A VALUE OF 4546 SQ
 FT FOR CARPET AND RUBBER PAD PLEASE REVIEW SHEET F-1
 INDICATING THE USE OF VCT TILE. PLEASE CORRELATE THE
 INPUT DATA REPORT TO PLANS. 13-400.A/ 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 10) SHEET A2 DETAIL 2 INDICATES A SOFFIT TO BE FASTENED
 TO DECK ABOVE BUT THERE IS NO INFORMATION AS TO SECURE
 THE SOFFIT TO THE DECK ABOVE.
  
 11A) SHEET A-5 DETAIL 2 & 9 BOTH INDICATE THE USE OF
 SUN SCREEN DETAIL, SHOP DRAWINGS TO BE SIGNED AND
 SEALED, PLEASE HAVE THEM DESIGNED TO 140 MPH WIND ZONE,
 EXPOSURE ???C???.
 1609.6.2.2 COMPONENTS AND CLADDING.
  
 11B) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE
 FOR SUPERVISING AND REVIEWING ALL PROJECT DATA,
 REPORTS, SHOP DRAWINGS ETC...
  
 12) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS
 INDICATE ANY COMPLIANCE FOR TERMITE PROTECTION. 1816.1
 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ???THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.???
  
  
 13A) SHEET A14 DUMPSTER ENCLOSURE IS NOT INDICATED ON
 THE STRUCTURAL PLANS,
 PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE PLAN:
 DESIGN PROCEDURE 1609.6.2
 1.THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3 . THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
 2. AN IMPORTANCE FACTOR, I W , SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.5 .
 3. AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.4 .
 4. A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, L ,
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1 (4).
  
 13B) SHEET A14 DUMPSTER ENCLOSURE FOOTER DOES NOT
 PROVIDE THE STRENGTH OF CONCRETE TO BE PLACED WITHIN
 THE FOOTER. 1805.4.2.1 CONCRETE STRENGTH. CONCRETE IN
 FOOTINGS SHALL HAVE A SPECIFIED COMPRESSIVE STRENGTH
 (F' C) OF NOT LESS THAN 2,500 POUNDS PER SQUARE INCH
 (PSI) (17 237 KPA) AT 28 DAYS.
  
 14) SHEET S-4 DETAIL# 2 INDICATES LIGHT GAUGE FRAMING
 BUT NO MENTION OF SHEATHING. INDICATES SEE
 ARCHITECTURAL PLANS. A5 DETAIL# 9 ALSO INDICATES THE
 USE OF 5/8 INCH SHEATHING BUT DOES NOT INDICATE WHAT
 TYPE OF SHEATHING IS TO BE USED.
  
 15) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 16) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 18) FEE BALANCE OF $8,025.60.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS. WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved