Plan Review Notes
Plan Review Notes For Permit 09020141
Permit Number 09020141
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-26 15:16:23DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL CODE
 FBC-2004 CHAPTER 1
  
 1. THE PLANS SHOW DETAILS THAT ARE NOT CLEAR OR
 LEGIBLE. (SEE VENT DETAIL, MAIN DRAIN DETAIL,
 ATMOSPHERIC VENT DETAIL ETC). SECTION 106.1.1
 CONSTRUCTION DOCUMENTS.
  
 2. A TIME CLOCK IS REQUIRED FOR RESIDENTIAL POOLS PER
 SECTION 13-612.1.ABC.2.3.3 AND A POOL COVER IS REQUIRED
 PER SECTION 13-612.1.ABC.2.3.2. PLEASE INDICATE THESE
 REQUIREMENTS ON THE PLANS.
  
 3. THE POOL PIPING SCHEMATIC DOES NOT REFLECT THE POOL
 PLAN. THE SCHEMATIC SHOWS SPA MAIN DRAINS AND SPA INLET
 BUT NO SPA IS INDICATED ON THE POOL LAYOUT. PLEASE
 CORRELATE. SECTION 106.1.1
  
 4. THE POOL PIPING SCHEMATIC DOES NOT SHOW A POOL
 HEATER, BUT THERE IS A POOL HEATER MANUFACTURE
 SPECIFICATION SHEET SUBMITTED. PLEASE CLARIFY. SECTION
 106.1.1.
  
 5. FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES).
  
 6. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES).
  
 7. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES).
  
 8. FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES).
  
 9. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF. (MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT). -- NOT SHOWN ON MANUF.
 SHEETS.
  
 10. FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  