2009-02-26 15:16:23 | DENIED |
| REFERENCE: |
| FBC-2004 RESIDENTIAL CODE |
| FBC-2004 CHAPTER 1 |
| |
| 1. THE PLANS SHOW DETAILS THAT ARE NOT CLEAR OR |
| LEGIBLE. (SEE VENT DETAIL, MAIN DRAIN DETAIL, |
| ATMOSPHERIC VENT DETAIL ETC). SECTION 106.1.1 |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. A TIME CLOCK IS REQUIRED FOR RESIDENTIAL POOLS PER |
| SECTION 13-612.1.ABC.2.3.3 AND A POOL COVER IS REQUIRED |
| PER SECTION 13-612.1.ABC.2.3.2. PLEASE INDICATE THESE |
| REQUIREMENTS ON THE PLANS. |
| |
| 3. THE POOL PIPING SCHEMATIC DOES NOT REFLECT THE POOL |
| PLAN. THE SCHEMATIC SHOWS SPA MAIN DRAINS AND SPA INLET |
| BUT NO SPA IS INDICATED ON THE POOL LAYOUT. PLEASE |
| CORRELATE. SECTION 106.1.1 |
| |
| 4. THE POOL PIPING SCHEMATIC DOES NOT SHOW A POOL |
| HEATER, BUT THERE IS A POOL HEATER MANUFACTURE |
| SPECIFICATION SHEET SUBMITTED. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| |
| 5. FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES). |
| |
| 6. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| R4101.9 WATER SUPPLY, LOCAL ORD. |
| #2853-95, BACKFLOW REQUIRED ON WATER |
| SERVICE. (ADD TO NOTES). |
| |
| 7. FBC-2004 SEC. 424.2.12.1, OR |
| FBCR-2004 SEC. R4101.12.1 PRESSURE |
| TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| NO AIR TEST SHALL BE APPROVED FOR PVC |
| PIPE AND FITTINGS. (ADD TO NOTES). |
| |
| 8. FBC-2004 SEC. 424.2.13.2, OR |
| FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| CONNECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES). |
| |
| 9. FBC-2004 SEC. 424.2.14.2, OR |
| FBCR-2004 SEC. R4101.14.2 WATER |
| RETENTION, PROVIDE A POSITIVE MEANS OF |
| RETAINING WATER IN THE HEATER WHEN PUMP |
| IS SHUT OFF. (MANUFACTURE SHEETS |
| REQUIRED, PLEASE SUBMIT). -- NOT SHOWN ON MANUF. |
| SHEETS. |
| |
| 10. FBC-2004 SEC. 424.2.14.4, OR |
| FBCR-2004 SEC. R4101.14.4 CONNECTIONS, |
| ALL WATER HEATING EQUIPMENT SHALL BE |
| INSTALLED WITH FLANGES OR UNION |
| CONNECTIONS ADJACENT TO THE HEATER. |
| (ADD TO NOTES). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |