2009-02-09 07:40:12BUILDING PLAN REVIEW
 PERMIT: 09020117
 ADD: 1 NORTH CLEMATIS 2ND FLOOR.
 CONT: BUTLER CONSTRUCTION
 TEL: (561)832-9700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THE DRAWINGS FAIL TO INDICATE THE TYPE OF WALL WHICH
 CONNECTS THE DOORS TO THE EXISTING WALL. PROVIDE
 INFORMATION SHOWING THE TYPE OF WALL WHICH IS SMALLER
 THAN THE EXISTING WALL. ADDITIONAL INFORMATION IS
 REQUIRED INCLUDING THE CONNECTION OF THE NEW WALL TO
 THE EXISTING WALL AND THE STRUCTURE ABOVE. 106.1.2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
  