Plan Review Notes
Plan Review Notes For Permit 09020092
Permit Number 09020092
Review Stop Z
Sequence Number 1
Notes
Date Text
2009-02-12 14:10:351) THE CITYPLACE DRI REQUIRES THAT ALL ROOFTOP
 MECHANICAL EQUIPMENT BE SCREENED FROM PUBLIC VIEW
 THROUGH ANY COMBINATION OF WALLS AND EQUIPMENT
 LOCATION.
  
 2) PLEASE PROVIDE DETAILS ON THE HEIGHT OF TOTAL HEIGHT
 OF THE EQUIPMENT ABOVE THE ROOF DECK, THIS INCLUDES THE
 BASE RACK.
  
 3) PLEASE PROVIDE ADDITIONAL DETAIL ON THE ROOF PLAN,
 SPECIFICALLY, LABEL THE NEW CONDENSER, PROVIDE
 DIMENSIONS TO THE EDGE OF THE ROOF, AND DETAIL THE
 HEIGHT AND LOCATION OF ANY PARAPETS OR WALLS USED TO
 SCREEN THE PROPOSED EQUIPMENT.
  
 4) CITYPLACE STAMP REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  