2009-02-15 13:33:20 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. A SEPARATE INSTALLATION DETAIL FOR THE ROOFTOP | | CONDENSER STAND WAS PROVIDED WITH THIS PERMIT | | APPLICATION. THIS DETAIL DOES NOT CORRESPOND WITH THE | | DETAIL PROVIDED ON MASTER PERMIT PLANS. WHICH IS TO BE | | USED? PLEASE COORDINATE PLANS WITH SUBMITTAL | | DOCUMENTATION. | | | | 2. PRE-ENGINEERED A/C STANDS ARE DEFINED AS STRUCTURAL | | COMPONENTS PER FAC RULE 9B-72. PRODUCT APPROVAL IS | | REQUIRED. THE SUBMITTAL DOES NOT INDICATE THIS PRODUCT | | HAS BEEN APPROVED BY THE FLORIDA PRODUCT APPROVAL | | SYSTEM. PROVIDE A COMPLETE FLORIDA PRODUCT APPROVAL | | SUBMITTAL WHICH HAS BEEN APPROVED IN WRITING BY THE | | MASTER PERMIT DESIGNER OF RECORD IN ACCORDANCE WITH | | FBC-B 106.3.3. IF THE INTENT IS TO APPLY FOR A LOCAL | | PRODUCT APPROVAL, PLEASE CONTACT A BUILDING PLANS | | EXAMINER FOR ADDITIONAL INFORMATION REGARDING THIS | | PROCESS. | | | | 3. WHEN RESUBMITTING, PLEASE BE SURE TO ADDRESS ALL | | ZONING PLAN REVIEW COMMENTS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|