2009-02-15 13:33:20REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A SEPARATE INSTALLATION DETAIL FOR THE ROOFTOP
 CONDENSER STAND WAS PROVIDED WITH THIS PERMIT
 APPLICATION. THIS DETAIL DOES NOT CORRESPOND WITH THE
 DETAIL PROVIDED ON MASTER PERMIT PLANS. WHICH IS TO BE
 USED? PLEASE COORDINATE PLANS WITH SUBMITTAL
 DOCUMENTATION.
  
 2. PRE-ENGINEERED A/C STANDS ARE DEFINED AS STRUCTURAL
 COMPONENTS PER FAC RULE 9B-72. PRODUCT APPROVAL IS
 REQUIRED. THE SUBMITTAL DOES NOT INDICATE THIS PRODUCT
 HAS BEEN APPROVED BY THE FLORIDA PRODUCT APPROVAL
 SYSTEM. PROVIDE A COMPLETE FLORIDA PRODUCT APPROVAL
 SUBMITTAL WHICH HAS BEEN APPROVED IN WRITING BY THE
 MASTER PERMIT DESIGNER OF RECORD IN ACCORDANCE WITH
 FBC-B 106.3.3. IF THE INTENT IS TO APPLY FOR A LOCAL
 PRODUCT APPROVAL, PLEASE CONTACT A BUILDING PLANS
 EXAMINER FOR ADDITIONAL INFORMATION REGARDING THIS
 PROCESS.
  
 3. WHEN RESUBMITTING, PLEASE BE SURE TO ADDRESS ALL
 ZONING PLAN REVIEW COMMENTS.
  