Plan Review Notes
Plan Review Notes For Permit 09020082
Permit Number 09020082
Review Stop M
Sequence Number 2
Notes
Date Text
2009-04-02 13:46:50PLAN DENIED
 1) PLEASE REFER TO TABLE 403.3 2007 FBC (M) FOR
 BATHROOM EXHAUST 50 CFM PER WATER CLOSET .
 2) PLEASE PROVIDE DUCT SIZE FOR EXISTING SLOT DIFFUSERS
 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732