2009-02-17 14:51:44DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. ALL SHEETS WITH BIRSE DESIGN INC TITLE BLOCK. PER
 FAC 61G1-16.004(2) THE FIRM ADDRESS IS REQUIRED. THE
 ADDRESS INDICATED IN THE TITLE BLOCKS, (1511 PROSPERITY
 FARMS ROAD LAKE PARK FLORIDA), DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE,
 (10096 SEAGRAPE WAY PALM BEACH GARDENS FLORIDA). FS
 481.2055. PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR
 WEBSITE TO MATCH PRIOR TO RESUBMITTING FOR REVIEW.
  
 2. SHT A-1 PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 BREAK ROOM SINK AND THE TURNING AREA AS REQUIRED IN
 CHAPTER 11 SECTIONS 11-4.24.5 AND 11-4.2.3.
  
 3. SHT A-1 DEMO NOTE 4 INDICATES THE SANITARY/WASTE
 LINES TO BE CAPPED OFF FLUSH WITH THE FLOOR. PER
 SECTION 704.5 IN THE REMOVAL OF ANY PART OF A SANITARY
 SYSTEM, DEAD ENDS ARE PROHIBITED. LINES SHALL BE CAPPED
 OFF WITHIN 2 FEET OF A LIVE BRANCH LINE OR COMPLETLY
 REMOVED. PLEASE INDICATE ON PLANS.
  
 4. SHT A-3 DETAIL 1 NOTE INDICATES THAT A GARBAGE
 DISPOSAL SHALL BE PROVIDED. SUBMIT A CUT DETAIL SHOWING
 THE SINK & GARBAGE DISPOSAL AND THE REQUIRED CLEARANCES
 PER SECTION 11-4.24.3. SUBMIT THE MANUF. SPECIFICATIONS
 FOR THE SINK AND THE GARBAGE DISPOSAL THAT INDICATE ADA
 APPROVAL. SECTION 106.1.2.
  
 5. SHT P-2 A TRAP PRIMER IS REQUIRED FOR THE HUB DRAIN
 PER SECTION 1002.4.
  
 6. SHT P-2 THE WATER HEATER SHALL BE RAISED ABOVE THE
 OUTLET OF THE HEATER PAN SO THAT THE HEATER DOES NOT
 SIT IN THE WATER FROM THE EXPANSION VALVE WATTS #530C.
 PLEASE INDICATE ON WATER HEATER DETAIL.
  
 7. SHTS P-1 KEY NOTES #4 INDICATES THE WATER HEATER IS
 A 40 GAL LOW BOY. PLEASE SUBMIT A DETAIL SHOWING HOW
 THE WATER HEATER WILL BE HANGING ABOVE THE CEILING. THE
 WEIGHT OF THE WATER HEATER WHEN FULL WILL BE OVER 375
 LBS AND PER SECTION 501.4 SHALL BE PROVIDED WITH ACCESS
 FOR OBSERVATION, MAINTENANCE, SERVICING AND
 REPLACEMENT. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  