Plan Review Notes
Plan Review Notes For Permit 09020082
Permit Number 09020082
Review Stop M
Sequence Number 1
Notes
Date Text
2009-02-15 11:03:47REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1: NOTE #15 CALLS FOR NEW DUCT PENETRATION OF
 SHAFT ENCLOSURE WITH FIRE DAMPER FOR OUTSIDE AIR. SHAFT
 ENCLOSURES THAT ARE PERMITTED TO BE PENETRATED BY DUCTS
 AND AIR TRANSFER OPENINGS SHALL BE PROTECTED WITH
 APPROVED FIRE AND SMOKE DAMPERS INSTALLED IN ACCORDANCE
 WITH THEIR LISTING PER FBCM 607.5.5.1.
  
 2. PAGE M-1: IS THE CEILING SPACE ABOVE THE EXISTING
 BATHROOMS ISOLATED FROM THE PLENUM CEILING ON THE REST
 OF THE FLOOR? NOTE ON THIS PAGE INDICATES THE CEILING
 SPACE THROUGHOUT IS A RETURN AIR PLENUM.THE DUCT ON THE
 DISCHARGE SIDE OF PROPOSED NEW EF-1 WILL BE UNDER
 POSITIVE PRESSURE AND CANNOT BE LOCATED IN A PLENU IN
 ACCORDANCE WITH FBCM 601.3.
  
 3. M AND P PAGES: MECHANICAL DETAIL CALLS FOR AUXILIARY
 DRAIN PAN WITH A FLOAT SWITCH AND NO SECONDARY DRAIN
 LINE WHILE PLUMBING PLAN SHOWS SECONDARY DRAIN LINE RUN
 FROM THE AUXILIARY DRAIN PAN TO ABOVE A SINK. WHICH IS
 CORRECT? PLEASE COORDINATE PLANS AND SHOW COMPLIANCE
 WITH FBCM 307.2.3.
  