Plan Review Notes
Plan Review Notes For Permit 09020012
Permit Number 09020012
Review Stop B
Sequence Number 3
Notes
Date Text
2009-03-05 13:50:37REVISE SHEET 1 OF 1, FBC3101. (DESIGN CRITERIA STATES
 FABRIC TO BE REMOVED WHEN WINDS EXCEED 90 AND THE FRAME
 IS DESIGNED TO 75 - DOES NOT COMPLY WITH MINIMUM CODE.
 CALCULATIONS ARE FOR DESIGN TO 90MPH)
  
 **AT CONTRACTOR'S RISK**