Plan Review Notes
Plan Review Notes For Permit 09020012
Permit Number 09020012
Review Stop B
Sequence Number 2
Notes
Date Text
2009-02-25 15:42:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. FBC3105.4, DESIGN CRITERIA FOR FABRIC REMOVAL DOES
 NOT MEET THE MINIMUM CODE REQUIREMENT. PLEASE REVISE.
  
 2ND REVIEW, THE SAME ENGINEERING DATED 10/13/08 WAS
 SUBMITTED. SEE SHEET 1 OF 1, GENERAL NOTE 4. FRAMES
 WITH FABRIC ARE TO BE DESIGNED TO WITHSTAND 90MPH AND
 FABRIC REMOVED WHEN WINDS EXCEED 75MPH, ALSO "NOTE TO
 OWNER" INCORRECT. ALSO SEE CALCULATIONS, DESIGN
 CRITERIA (SHEET 3) STATE SHADE COVERING TO BE REMOVED
 WHEN WINDS EXCEED 90; THIS DOES NOT COMPLY WITH
 FBC3105.4. PLEASE CHECK ALL SHEETS AND REVISE ALL
 SHEETS TO MEET MINIMUM REQUIREMENTS OF FBC3105.4.
  
 NEW COMMENT:
  
 2. ALL INFORMATION REQUIRED BY FAC61G15-23.002 REQUIRED
 ON EACH SHEET, SEE PAGE 1 OF 1.
  