Plan Review Notes
Plan Review Notes For Permit 09020012
Permit Number 09020012
Review Stop B
Sequence Number 1
Notes
Date Text
2009-02-17 15:45:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC3105.4, DESIGN CRITERIA FOR FABRIC REMOVAL DOES
 NOT MEET THE MINIMUM CODE REQUIREMENT. PLEASE REVISE.
  
 2. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 3. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved