2009-09-03 08:25:55 | 09/03/09 PASSED WITH PROVISOS |
| |
| REVIEW FOR STORMWATER ELEMENTS AT 233 WENNONAH PLACE |
| |
| #1 STORM CALCULATIONS DATED 09/02/09 HAVE BEEN RECEIVED |
| AND APPROVED. |
| CONTRACTOR SHALL BUILD THE PARKING AREA BASED ON THE |
| CALCULATIONS SUPPLIED AND REVISE |
| THE AS-BUILT PLAN ACCORDINGLY. (CALCS ARE ATTACHED TO |
| THE PLAN) |
| |
| #2 SHEET ONE DOES NOT AGREE WITH THE PLAN SHOWN ON SHT |
| 2 A (NO HANDICAP PARKING SHOWN) |
| ( CONTRACTOR NEEDS TO BUILD AS PER CITY APPROVED SITE |
| PLAN.) |
| |
| CONTRACTOR SHALL BE RESPONSIBLE FOR THIS CORRECTION |
| DURING CONSTRUCTION: |
| |
| #1 SHEET 2B PAVING AND DRAINAGE DETAILS: |
| PRECAST INLET TYPE "C" (OPTION) DETAIL NEEDS TO SHOW OR |
| STATE THAT ROCK UNDER STRUCTURE MUST BE WRAPPED IN |
| FILTER FABRIC |
| #2 SHEET 2B PAVING AND DRAINAGE DETAILS: |
| EXFILTRATION TRENCH DETAIL (OPTION) |
| REVISE NOTE #2 TO INCLUDE "BOTTOM" ALSO. |
| #3 SHEET 2B PAVING AND DRAINAGE DETAILS: |
| ADD TO 12"X12" SUMP A NOTE ADDING SS HARDWARE CLOTH |
| (MESH) AT SUMP ENTRY POINT. |
| #4 SHEET 2B PAVING AND DRAINAGE DETAILS: |
| REVISE NOTE #2 TO INCLUDE "BOTTOM" ALSO. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF ANY FURTHER QUESTIONS |
| OR CONCERN. |
| |