Date |
Text |
2009-04-01 11:59:08 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT IR-1 MINIMUM TWO SETS OF SIGNED/SEALED PLANS |
| REQUIRED PER SECTION 106.1. PLEASE SUBMIT REQUIRED SETS |
| OF PLANS WITH APPLICATION. |
| |
| 2. SHT IR-1 SHALL BE SIGNED, SEALED AND DATED. THE |
| SHEET HAS NOT BEEN SEALED AND THE SIGNATURE IS A PHOTO |
| COPY OF AN ORIGINAL SIGNATURE. ORIGINAL "WET |
| SIGNATURES" ARE REQUIRED ON EACH SET OF PLANS. SECTION |
| 106.1, FAC 61G1-16.004(2) & FS 481.306. |
| |
| 3. SHT IR-1 THE METER, PVB, RAIN SENSOR & THE |
| CONTROLLER LOCATIONS ARE TO BE INDICATED ON THE PLANS. |
| SECTION 106.1.1 & APPENDIX "F" (J) & FS 373.62. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |