2009-01-30 12:02:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE PROPERTY IS LOCATED IN EXPOSURE C. PLEASE REVISE
 DESIGN PRESSURES ACCORDINGLY. FBC1609.4, FBC
 R301.2.1.4.
  
 2. MINIMUM STRENGTH FOR CONCRETE IS SPECIFIED ON SHEET
 6 OF THE PRODUCT APPROVAL; IN THIS CASE, 3320PSI.
 PLEASE EITHER PROVIDE EVIDENCE THAT THE CONCRETE MEETS
 THIS MINIMUM REQUIREMENT, OR USE ANCHOR SPACING FOR
 HOLLOW BLOCK.
  
  
  