2009-01-29 10:00:15BUILDING PLAN REVIEW
 PERMIT: 09010401
 ADD: 100 N CLEMATIS ST
 CONT: CATALFUMO
 TEL: (561)282-8265
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 2) SHEET S-3 UNDER NOTE# 9 CAST IN PLACE CONCRETE PILES
 (AUGER PILES)
  
 2A) NOTE (A) HAS THREE ISSUES THE PILE DESCRIPTION HAS
 LEFT OUT BEHIND 14 (INCHES),
  
 2B) NOTE (A) THE UNIT OF WEIGHT WAS LEFT OF BEHIND THE
 (10) KIPS, TONS UNKNOWN, 10 ALLOWABLE TENSION CAPACITY
  
 2C) NOTE (A) INDICATES 5 KIPS LATERAL CAPACITY, WHILE
 THE AUGER PILE REPORT FROM ARDAMAN INDICATES A YIELD OF
 1 TON( 2KIPS), WITH THE SOILS REPORT ONLY OBTAINING 2
 KIPS LATERAL LOADING OUT OF A 14" AUGER PILE
 WOULD A LARGER PILE BE REQUIRED TO ACHIEVE THE 5 KIPS
 LATERAL LOADING REQUIRED BY THE PILE DESIGN ON SHEET
 S-3?
  
 3) ARDAMANS SOILS REPORT# 08-2035 INDICATES THE USE OF
 14 INCH DIAMETER AUGERCAST PILE INSTALLED TO DEPTHS OF
 APPROXIMATELY 40 FEET. SECTION 1810.3.2 THE PILE LENGTH
 SHALL NOT EXCEED 30 TIMES THE AVERAGE DIAMETER. THE
 MINIMUM DIAMETER SHALL BE 12 INCHES (305 MM).
 EXCEPTION: THE LENGTH OF THE PILE IS PERMITTED TO
 EXCEED 30 TIMES THE DIAMETER, PROVIDED THAT THE DESIGN
 AND INSTALLATION OF THE PILE FOUNDATION ARE UNDER THE
 DIRECT SUPERVISION OF A REGISTERED DESIGN PROFESSIONAL
 KNOWLEDGEABLE IN THE FIELD OF SOIL MECHANICS AND PILE
 FOUNDATIONS. THE REGISTERED DESIGN PROFESSIONAL SHALL
 CERTIFY TO THE BUILDING OFFICIAL THAT THE PILES WERE
 INSTALLED IN COMPLIANCE WITH THE APPROVED CONSTRUCTION
 DOCUMENTS.
  
 30 TIMES THE PILE DIAMETER OF 14 INCHES EQUALLS 420
 INCHES. THE PILE LENGTH OF 40 FEET EXPRESED IN ICHES IS
 480 INCHES WHICH EXCEEDS THE ALLOWABLE 420INCHES. THE
 EXCEPTION DOES ALLOW FOR THE PILE TO BE DEEPER UNDER
 THE DIRECT SUPERVISION OF A REGISTERED DESIGN
 PROFESSIONAL. SHEET S-3 AUGERCAST PILE NOTE (G) THE
 CONTRACTOR SHALL ENGAGE THE SERVICES OF A REGISTERED
 PROFESSIONAL ENGINEER TO SUPERVISE AND CERTIFY THAT THE
 PILE INSTALLATION WORK COMPLIES WITH THE DESIGN
 REQUIREMENTS. WE HAVEN'T SEEN ANY DOCUMENTS FROM THE
 CONTRACTOR INDICATING COMPLIANCE WITH THIS SECTION.
 ALSO NOTE THREE SETS OF ALL DOCUMENTS WILL NEED TO BE
 SUBMITTED, ONE FOR THE SOILS ENGINEER.
  
 4) SHEET S-3 CAST IN PLACE CONCRETE PILE NOTE "B"
 INDICATES THE AUGER PILE TO INSTALL 5,000 PSI CONCRETE
 WHILE THE SOILS REPORT FROM ARDAMAN INDICATES THE USE
 OF 4,500 PSI CONCRETE GROUT. PLEASE CORRELATE PLANS AND
 SOILS REPORT.
  
 5) DEALS WITH THE RECOMMANDATION OF THE SOILS ENGINEER
 THAT THE PILE SPACING OF MINIMUM SPACING OF 3.5 FEET ON
 CENTER. THE STRUCTURAL SHEET S-1 THE AUGER PILE ARE
 SPACED MORE THAN 3.5 FEET APART.
 DISCREPANCY IN PLANS, ADDITIONAL INFORMATION REQUIRED,
 106.1.2.
  
 6) ALSO DEALS WITH THE WORDING OR INTERPRETATION OF
 PILES SHOULD NOT BE INSTALLED WITHIN 5 FEET OF ANY
 PILE. THE NOTE DOES NOT INDICATE IF THESE ARE CENTER TO
 CENTER OR FROM EDGE TO EDGE. SECTION 1810.3.3
 INDICATES THAT AUGER CAST PILES SHALL NOT BE INSTALLED
 WITHIN SIX PILE DIAMETER CENTER TO CENTER OF PILE
 FILLED WITH CONCRETE LESS THAN 12 HOURS OLD. PLEASE
 CLARIFY THE LANGUAGE USED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.