Date |
Text |
2009-02-06 08:51:25 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. SECTION 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION |
| DOCUMENTS, SPECIAL INSPECTION AND STRUCTURAL |
| OBSERVATION PROGRAMS, AND OTHER DATA SHALL BE SUBMITTED |
| IN TWO OR MORE SETS WITH EACH APPLICATION FOR A PERMIT. |
| ONLY TWO SETS OF PLANS WERE SUBMITTED WITH TWO PERMIT |
| APPLICATIONS. EITHER SUBMIT 2 SETS WITH EACH |
| APPLICATION, OR APPLY FOR ALL WORK ON ONE APPLICATION. |
| |
| 2. SHT A-1.0 APPLICABLE CODES TO INCLUDE THE 2007 |
| AMENDMENTS TO THE FBC-2004 PLUMBING AND INCLUDE |
| FBC-2004 BUILDING CODE W/2007 AMENDMENTS. |
| |
| 3. SHTS P-1.0 & P-2.0 SHOW DRINKING FOUNTAINS TO THE |
| RIGHT OF THE CENTER STAIRS/ELEVATORS. WILL THESE |
| DRINKING FOUNTAINS REMAIN? PLEASE CLARIFY. SECTION |
| 106.2.1. MORE INFORMATION IS REQUIRED. IF DELETING THE |
| EXISTING DRINKING FOUNTAINS, IN THE REMOVAL OF ANY PART |
| OF A DRAINAGE SYSTEM, DEAD ENDS ARE PROHIBITED. SECTION |
| 704.5. |
| |
| 4. INFORMATIONAL: A SEPARATE PLUMBING PERMIT IS |
| REQUIRED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |