2010-04-12 14:08:20 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| |
| |
| ****UPDATE***** |
| PLUMBING ISOMETRIC REQUIRED FOR ISSUANCE OF PERMIT |
| |
| |
| |
| 1. THERE APPEAR TO BE 6 SINKS ON A 2" COMBINATION DRAIN |
| AND VENT ON THE EAST SIDE OF THE HOUSE. P3111.3 SIZE - |
| 12 FIXTURE UNITS REQUIRE 3" PIPE. IF NOT A COMBINATION |
| WASTE AND VENT, 4 OF THE SINKS ARE MISSING VENTS. |
| |
| 2. A MINIMUM OF ONE VENT STACK THROUGH THE ROOF IS |
| REQUIRED. |
| P3102.1 STACK REQUIRED. |
| EVERY BUILDING SHALL HAVE A VENT STACK OR A STACK VENT. |
| SUCH VENT SHALL RUN UNDIMINISHED IN SIZE AND AS |
| DIRECTLY AS POSSIBLE FROM THE BUILDING DRAIN THROUGH TO |
| THE OPEN AIR ABOVE THE ROOF. |
| |
| 3. THE 2 SINKS CONNECTED TO THE WATER CLOSET ARE NOT |
| PERMITTED TO BE CONNECTED WITH A HEEL OR SIDE INLET 1/4 |
| BEND. ALSO, SINKS ARE NOT PERMITTED TO BE PART OF A WET |
| VENT. IF THE THREE WC;S ARE IN A CIRCUIT VENT, THEN A |
| VERTICAL DRY VENT IS REQUIRED BETWEEN THE TWO WC'S. |
| P3110.2 VENT CONNECTION. |
| THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| THE TWO MOST UPSTREAM FIXTURE DRAINS. |
| |
| 4.THE 2 LAVS SHOWN WITH THE SINGLE WC ARE DRAWN AS AN |
| S-TRAP |
| |
| 5. THE TWO DF STACKS REQUIRE VENTING. |
| |
| 6. 3/4" WATER PIPE IS REQUIRED FOR 3 OR MORE FIXTURES. |
| 3/4" HOT WATER PIPE IS REQUIRED FOR 5 OR MORE FIXTURES. |
| OR CALCULATIONS |
| SHOWING THAT 1/2" WOULD BE ADEQUATE |
| P2903.1 WATER SUPPLY SYSTEM DESIGN CRITERIA. |
| THE WATER SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL |
| BE DESIGNED AND PIPE SIZES SHALL BE SELECTED SUCH THAT |
| UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE |
| POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN |
| IN TABLE P2903.1. TABLE P2903.2B SHALL BE PERMITTED TO |
| BE USED TO SIZE THE WATER SERVICE OR WATER DISTRIBUTION |
| SYSTEM. |
| |
| REVIEW BY LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| (561) 805-6692 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |
| |
| |