2009-03-06 14:23:23 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NO ELECTRICAL PLANS WHERE SUBMITTED FOR REVIEW.
 SUBMIT PLANS INDICATING THE SCOPE OF WORK INTENDED.
 106.1 FBC
  
 2} INDICATE WHAT THE USE AND OCCUPANCY OF THE BUILDING
 IS INTENDED TO BE PER CHAPTER 3 FBC.
  
 3} 301.5 EXISTING BUILDING CODE
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. INDICATE SAME
 ON THE PLANS.
  
 4} 106.1.3 RESERVED. QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  