Date |
Text |
2009-03-03 16:33:35 | |
| BUILDING PLAN REVIEW |
| PERMIT: 090100345 |
| ADD: 724 BUNKER RD |
| CONT: TROPICAL PLUMBING |
| TEL: (561)856-6655 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 3) SUBMIT A PROPOSED AND AN EXISTING FLOOR PLAN OF THE |
| SPACE. THESE DRAWING SHALL SHOW ALL AREAS WHERE WORK |
| SHALL BE PERFORMED. PROVIDE A WALL LEGEND INDICATING |
| THE TYPE OF WALL TO BE CONSTRUCTED AND WHICH ONES WILL |
| BE DEMOED. 2004 FBC 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 4) NOTE: THE FLOOR PLANS SUBMITTED DO NOT MATCH WHAT WE |
| HAVE ON RECORD. THEREFORE, IF WORK WAS CARRIED OUT AT |
| THIS LOCATION WITHOUT PERMITS A FEE MAY BE APPLIED TO |
| THIS PERMIT APPLICATION. IF THE OWNER CAN PROVIDE |
| INFORMATION FROM THIS BUILDING DEPARTMENT REGARDING THE |
| INTERIOR REMODEL OF THE STRUCTURE, THERE WILL BE NO |
| FEE. |
| |
| 5) FBC 106: THE PLANS SUBMITTED SHALL BE OF DRAFTSMAN |
| QUALITY AND SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. |
| SUBMIT TWO COMPLETE SETS OF PLANS PREPARED BY A DESIGN |
| PROFESSIONAL THAT IS REGISTERED WITH THE STATE OF |
| FLORIDA. PLANS PREPARED BY A DESIGN PROFESSIONAL SHALL |
| BEAR THE DESIGNER OFFICIAL SEAL, SIGNATURE AND DATE ON |
| EACH SHEET. FLORIDA STATUTES 471 AND 481. |
| |
| 6) FBC 108.4 ANY PERSON WHO COMMENCES ANY WORK ON A |
| BUILDING, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| PLUMBING SYSTEM BEFORE OBTAINING THE BUILDING |
| OFFICIAL???S APPROVAL OR THE NECESSARY PERMITS SHALL BE |
| SUBJECT TO A PENALTY OF 300 PERCENT OF THE USUAL PERMIT |
| FEE IN ADDITION TO THE REQUIRED PERMIT FEES. |
| |
| 7) FBC 313: MORE INFORMATION IS REQUIRED TO SHOW THE |
| TYPE OF DAY-CARE FACILITY AT THIS LOCATION. INDICATE |
| THE NUMBER OF OCCUPANTS / CLIENTS WHO WILL RECEIVE |
| CARE, MAINTENANCE AND SUPERVISION BY SOMEONE OTHER THAN |
| THEIR RELATIVE OR LEGAL GUARDIAN. INDICATE THE OCCUPANT |
| LOAD PER TABLE 1004, THE PROPOSE USE AND OCCUPANCY PER |
| CHAPTER 3 AND THE TYPE OF CONSTRUCTION PER TABLE 601 |
| AND TABLE 503 |
| |
| 8) 2004 FBC (EXISTING) 301.5 A DESIGN PROFESSIONAL OR |
| AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. THIS INFORMATION SHALL BE SHOWN ON THE |
| PLANS. |
| |
| 9) FBC 11-4.3. INDICATE THE ACCESSIBLE ROUTE TO THE |
| BUILDING, THE ACCESSIBLE ROUTE SHALL. TO THE MAXIMUM |
| EXTENT FEASIBLE, COINCIDE WITH THE ROUTE FOR THE |
| GENERAL PUBLIC. THE MAIN ENTRANCE TO THE BUILDING SHOWS |
| AT LEAST TWO STEPS, WHICH WILL NOT MEET THE ACCESSIBLE |
| REQUIREMENT; SEE SECTION 11-4.8 FOR RAMP REQUIREMENTS. |
| IF PARKING SPACES ARE PROVIDED; THE ACCESSIBLE SPACE |
| SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE |
| ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| ENTRANCE11-406.2. |
| |
| 10) FBC (EXISTING) 812.4.1.1 WHEN A CHANGE OF OCCUPANCY |
| GROUP IS MADE TO A HIGHER HAZARD CATEGORY (LOWER |
| NUMBER) AS SHOWN IN TABLE 812.4.1, THE MEANS OF EGRESS |
| SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE |
| FBC. PROVIDE A LIFE SAFETY PLAN SHOWING THE MEANS OF |
| EGRESS, EXIT ACCESS, EXIT, EXIT DISCHARGE AND THE DOORS |
| WITH THE DIMENSIONS. |
| |
| NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, |
| AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. FOR MORE INFORMATION SEE FBC (EXISTING) |
| CHAPTER 8. A PLUMBING CONTRACTOR CANNOT DO THE INTERIOR |
| REMODEL OF THE STRUCTURE. A BUILDING, RESIDENTIAL OR |
| GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMODEL |
| OF THE STRUCTURE. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| PHONE (561)805-6726 |
| FAX (561) 805-6676 |
| [email protected] |
| |