2009-09-18 14:18:56 | ** TEMPORARY FAILED REVIEW ** |
| |
| 1) NOTE: REVIEW IS IN TEMPORARY FAILED STATUS. THE |
| SUBMITTED REVISED ENERGY CALCULATIONS WERE NOT SEALED |
| WITH REQUIRED RAISED SEAL PER FAC 61G15-23.002, |
| FS471.025. ALL COPIES OF PLANS, SUBMITTED SUPPORTING |
| DOCUMENTS WHICH ARE DONE BY THE ENGINEER ARE REQUIRED |
| TO MEET SECTIONS AS NOTED. THIS INCLUDES |
| OWNERS/CONTRACTORS SETS OF PLANS. |
| CALLED CONTRACTOR AND LEFT MESSAGE AS THE SHEET 3 OF 8 |
| WHICH WAS SIGNED AND DATED BY THE ENGINEER MAY BE |
| DROPPED BY THE OFFICE TO PLACE IN SUBMITTED |
| CALCULATIONS. ONLY THE RAISED SEAL DID NOT GET DONE ON |
| SHEET. |
| ** RULES FROM THE ENGINEERING BOARD ARE MORE |
| RESTRICTIVE THAN THE ARCHITECTS BOARD WHICH ONLY |
| REQUIRES FILE SET TO BE DONE THE SAME. |
| |
| |
| 2) NOTE: A COLOR PHOTO-COPY WAS MADE OF SHEET C-2 WHICH |
| IS NOT PERMITTED. THIS IS A COLOR PHOTO-COPY OF PLANS |
| WHICH WERE SIGNED, DATED AND SEALED BY DESIGN |
| PROFESSIONAL. |
| DESIGNER OF RECORD MAY COME INTO OFFICE, RE-SIGN, DATED |
| AND SEAL SHEETS. |
| FAC 61G15-23.002, FS 471.025 |
| |
| 3) NOTE: IMPACT FEE REVIEW HAS BEEN PLACED IN FAILED |
| STATUS. THIS WAS NOT DONE BY BUILDING REVIEWER EVEN |
| THOUGH NOTED IN SYSTEM. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |