2009-11-19 09:07:05 | REVISION SUBMITTAL CHECKLIST. (ONLY 2 SETS OF |
| EVERYTHING IS REQUIRED). |
| |
| 1- DRESSING ROOM REVISION: OK. |
| |
| 2-TRUSS PACKAGE: |
| A) TRUSS LAYOUT AND TRUSS FT1 SHOW TRUSS BEARING ON A |
| WOOD LEDGER ON ONE SIDE AND BEARING ON THE WALL ON THE |
| OTHER SIDE. ROOF FRAMING PLAN ON STRUCTURAL DRAWINGS |
| SHOW TRUSS BEARING ON WOOD LEDGERS ON BOTH SIDES. |
| REVISE AS REQUIRED TO MATCH. |
| |
| B) NEED ENGINEER'S ORIGINAL SIGNATURE AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTE. |
| |
| C) REVISE INFORMATION ON TRUSS COVER PAGE. THIS IS NOT |
| A SINGLE FAMILY RESIDENCE AND THIS IS NOT BROWARD |
| COUNTY. REVISE AS REQUIRED. |
| |
| 3- PARKING LOT LIGHT POLE CALCULATIONS: NEED TO PROVIDE |
| 2 COPIES WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS |
| REQUIRED BY CHAPTER 471 FLORIDA STATUTE. ONLY ONE |
| ORIGINAL WAS SUBMITTED. |
| |
| 4- ROOFING BASE SHEET CALCULATIONS ARE OK. JUST MAKE |
| SURE THAT THE INSULATION TO BE INSTALLED MEETS THE R |
| VALUE SPECIFIED ON THE ENERGY CALCULATIONS. |
| |
| 5- ASBESTOS REPORT. WAITING FOR ENGINEER'S CURRENT |
| SEAL. |
| |
| 6- ROLL DOWN HURRICANE SHUTTERS: |
| A) REVISE TYPE OF ANCHOR TO BE USED. TYPE "A" IS FOR |
| 3000PSI CONCRETE. NEED TO USE TYPE "B" TAPCON FOR CMU |
| CONSTRUCTION. REVISE INSTALLATION SCHEDULE USING TYPE |
| "B" TAPCON TABLE FROM SHUTTERS DRAWINGS SUBMITTED (SEE |
| SHEET 4 OF 7). |
| |
| 7- ACCORDION SHUTTERS: OK. |
| |
| 8- INSWING SINGLE DOOR PRODUCT APPROVAL: OK. |
| |
| 9- OWES $130 FOR REVISION FEES. |
| |